Skip to main content
QUICK REVIEW

[论文解读] An IoT Framework for Building Energy Optimization Using Machine Learning-based MPC

Aryan Morteza, Hosein K. Nazari|arXiv (Cornell University)|Aug 23, 2024
Neural Networks and ApplicationsComputer Science被引用 3
一句话总结

本文提出了一种基于物联网(IoT)和机器学习的模型预测控制(MPC)框架,仅使用温度传感器和最少的建筑数据,对老旧建筑的暖通空调(HVAC)系统进行能效优化。通过采用人工神经网络(ANN)实时动态估算热力模型参数(结合气象和人员占用数据),该系统在保持用户舒适度的同时,与人工控制相比实现了57.59%的电力消耗降低,并兼容二进制(ON/OFF)控制器。

ABSTRACT

This study proposes a machine learning-based Model Predictive Control (MPC) approach for controlling Air Handling Unit (AHU) systems by employing an Internet of Things (IoT) framework. The proposed framework utilizes an Artificial Neural Network (ANN) to provide dynamic-linear thermal model parameters considering building information and disturbances in real time, thereby facilitating the practical MPC of the AHU system. The proposed framework allows users to establish new setpoints for a closed-loop control system, enabling customization of the thermal environment to meet individual needs with minimal use of the AHU. The experimental results demonstrate the cost benefits of the proposed machine-learning-based MPC-IoT framework, achieving a 57.59\% reduction in electricity consumption compared with a clock-based manual controller while maintaining a high level of user satisfaction. The proposed framework offers remarkable flexibility and effectiveness, even in legacy systems with limited building information, making it a pragmatic and valuable solution for enhancing the energy efficiency and user comfort in pre-existing structures.

研究动机与目标

  • 解决老旧建筑中因暖通空调(HVAC)系统过时且缺乏先进控制而导致的能源效率低下问题。
  • 克服获取详细建筑围护结构数据用于热力建模所带来的高成本与复杂性。
  • 通过数据驱动的热力模型,实现在仅配备基础控制器(如ON/OFF或PI/PID)的建筑中有效实施模型预测控制(MPC)。
  • 证明通过机器学习实现的实时自适应热力建模可显著提升能效,且无需重大基础设施升级。
  • 提供一种可扩展、低成本的解决方案,通过仅使用温度传感器和无线数据,为现有建筑实现智能能效优化。

提出的方法

  • 使用来自无线传感器网络(WSNs)的实时数据对人工神经网络(ANN)进行训练,数据包括室内外温度、湿度以及气象条件(如太阳辐射、风速)。
  • ANN动态估算随时间变化的热力模型参数(如传热系数),以实时反映建筑的热力动态特性。
  • 将估算出的参数用于模型预测控制(MPC)算法,以生成空调处理机组(AHU)系统的最优设定点。
  • 通过参数提取与信号映射,将MPC控制器适配为与老旧的二进制或模拟控制器(如ON/OFF、PI/PID)兼容。
  • 采用每小时数据整合策略,将气象扰动信息纳入机器学习模型,提升预测精度。
  • 在真实建筑中部署该框架,覆盖多个季节,通过传感器和反馈调查监测能耗与用户舒适度。
Figure 1: The experimental setup involved collecting stream data at five-minute intervals using Raspberry Pis. The collected data were then transmitted to the central server via the MQTT protocol, which enabled the AHU system to make decisions based on the occupants/administrators given a setpoint.
Figure 1: The experimental setup involved collecting stream data at five-minute intervals using Raspberry Pis. The collected data were then transmitted to the central server via the MQTT protocol, which enabled the AHU system to make decisions based on the occupants/administrators given a setpoint.

实验结果

研究问题

  • RQ1基于最少传感器数据训练的机器学习热力模型,能否有效替代详细建筑围护结构信息,用于老旧HVAC系统的MPC?
  • RQ2与传统的基于时钟的定时控制器相比,基于机器学习的MPC控制器在能耗和热舒适度方面的表现如何?
  • RQ3自适应的数据驱动热力模型在具有动态热力行为的建筑中,能在多大程度上提升MPC的准确性?
  • RQ4所提出的物联网框架能否在不进行硬件升级的前提下,有效集成到低成本的二进制HVAC控制器中?
  • RQ5在不同季节的实际运行条件下,该框架在真实世界中的节能潜力有多大?

主要发现

  • 所提出的基于机器学习的MPC-IoT框架在12周的测试期内,与基于时钟的手动控制器相比,实现了57.59%的电力消耗降低。
  • 尽管实现了显著的节能效果,系统仍保持了较高的用户满意度,该结论得到住户反馈调查的证实。
  • 基于ANN的热力模型仅使用温度和基本气象数据,即有效捕捉了动态热力行为,包括气象和人员占用带来的变化。
  • 该框架在供暖和制冷季节均表现出稳健性能,但夏季发现AHU冷却能力不足,导致湿度偏高和用户不适。
  • 与人工控制下的11,660 kW相比,采用物联网解决方案后能耗降低至约4920 kW,证实了显著的节能效果。
  • 该框架在建筑信息有限的建筑中依然有效,证明其在改造现有建筑方面的实际可行性。
Figure 2: The long-range sensor node was designed using a microcontroller and manufactured in this study.
Figure 2: The long-range sensor node was designed using a microcontroller and manufactured in this study.

阅读本论文

在 Nubint 阅读器中打开原文,边读边就任意段落提问。

在 Nubint 中阅读本论文

本解读由 AI 根据论文原文生成,引用前请核对原文。