[论文解读] Analysis of November 21, 2021, Kaua`i Island Power System 18-20 Hz Oscillations
论文识别了在植物跳闸后由逆变器资源引起的在Kaua‘i岛出现的18–20 Hz系统级振荡源,使用EMT模型重现,并提出两种在仿真中验证的缓解方法。
This letter discusses the 18-20 Hz oscillation event at 05:30 am on November 21, 2021, in Kaua`i's power system following the trip of an oil power plant. As far as the authors are aware, this is the first report of a transmission system-wide subsynchronous oscillation driven by inverter-based resources (though the system in question is relatively small). In this letter, we leverage two data-based methods-the dissipating energy flow method and the sub/super-synchronous power flow method-to locate the sources of the oscillation. Also, we build an electromagnetic transient model of the Kaua`i power system and replay the 18-20 Hz oscillation. Finally, we propose two mitigation methods and validate their effectiveness via numerical simulation.
研究动机与目标
- Identify the sources of the 18–20 Hz oscillations observed on Kaua‘i Island after a contingency event.
- Recreate the oscillation using an EMT power system model to validate understanding of dynamics.
- Develop and validate mitigation strategies to suppress the oscillation.
- Assess the effectiveness of inverter-based resource controls in damping system-wide subsynchronous oscillations.
- Suggest directions for future work including grid-forming controls and hardware-in-the-loop validation.
提出的方法
- Use two measurement-based methods (dissipating energy flow and sub/super-synchronous power flow) to locate oscillation sources from PMU and high-rate PoW data.
- Build an EMT (PSCAD) model of the Kaua‘i system with revised KIUC data and vendor models for IBRs to replay the 18–20 Hz event.
- Perform Prony analysis on IBR responses to identify mode shapes and relative phasing.
- Conduct parameter sensitivity studies in the EMT model to evaluate mitigation options.
- Validate EMT model accuracy by comparing simulated and recorded frequency and power responses (FFT spectra and time-domain traces).
- Propose two mitigation approaches: (1) adjust inverter-level P/f droop constant, (2) reduce PLL proportional gains in IBRs, and test their impact via EMT simulations.
实验结果
研究问题
- RQ1Where do the 18–20 Hz oscillations originate after the plant A trip on Kaua‘i Island?
- RQ2Can an EMT model replicate the observed oscillations and mode shapes to validate understanding of the dynamics?
- RQ3Do targeted changes to inverter controls mitigate the 18–20 Hz oscillations effectively in simulations?
- RQ4What is the role of grid-following versus grid-forming inverter controls in damping such oscillations on a small islanded grid?
主要发现
- Both DEF and sub/super-synchronous power flow analyses identify IBR1 and IBR2 as the oscillation sources.
- EMT simulations reproduce the 18–20 Hz oscillations and show IBR1 and IBR2 oscillating against IBR3 and IBR4, consistent with measurements.
- The IBRs’ energy exchanges and mode shapes during the event match between measurements and EMT results.
- Two mitigation options are effective in simulations: increasing the P/f droop from 3.0% to 4.0%, and reducing PLL gains from 0.15 to 0.10, both of which suppress the 18–20 Hz oscillations.
- KIUC subsequently converted IBR1 from grid-following to grid-forming, observed to mitigate the oscillations.
- Acknowledges potential for grid-forming IBR controls as a mitigation path and the value of further validation with hardware-in-the-loop or field tests.