Skip to main content
QUICK REVIEW

[论文解读] Data Center Cooling System Optimization Using Offline Reinforcement Learning

Xianyuan Zhan, Xiangyu Zhu|ArXiv.org|Jan 25, 2025
Heat Transfer and OptimizationEngineering被引用 3
一句话总结

论文提出一个带有图神经网络和时间反演对称性约束的物理信息离线强化学习框架(TTDM),用于优化数据中心制冷,在真实生产数据中心实现14–21%的能耗节省且无安全违规。

ABSTRACT

The recent advances in information technology and artificial intelligence have fueled a rapid expansion of the data center (DC) industry worldwide, accompanied by an immense appetite for electricity to power the DCs. In a typical DC, around 30~40% of the energy is spent on the cooling system rather than on computer servers, posing a pressing need for developing new energy-saving optimization technologies for DC cooling systems. However, optimizing such real-world industrial systems faces numerous challenges, including but not limited to a lack of reliable simulation environments, limited historical data, and stringent safety and control robustness requirements. In this work, we present a novel physics-informed offline reinforcement learning (RL) framework for energy efficiency optimization of DC cooling systems. The proposed framework models the complex dynamical patterns and physical dependencies inside a server room using a purposely designed graph neural network architecture that is compliant with the fundamental time-reversal symmetry. Because of its well-behaved and generalizable state-action representations, the model enables sample-efficient and robust latent space offline policy learning using limited real-world operational data. Our framework has been successfully deployed and verified in a large-scale production DC for closed-loop control of its air-cooling units (ACUs). We conducted a total of 2000 hours of short and long-term experiments in the production DC environment. The results show that our method achieves 14~21% energy savings in the DC cooling system, without any violation of the safety or operational constraints. Our results have demonstrated the significant potential of offline RL in solving a broad range of data-limited, safety-critical real-world industrial control problems.

研究动机与目标

  • 通过开发数据高效、安全的优化方法来降低数据中心制冷的高能耗成本。
  • 利用离线历史数据在没有高保真仿真器或在线探索的情况下学习策略。
  • 通过时间反演对称性和图神经网络引入物理知识以提升泛化能力。
  • 在真实世界生产数据中心和专用测试平台进行部署与验证。

提出的方法

  • 将数据中心制冷控制形式化为带安全感知奖励平衡能源使用与温度安全的离线MDP。
  • 提出TTDM:一个在图神经网络基础上强制实现T对称性的热力学动力学模型,捕捉时空与控制依赖关系。
  • 在潜在空间中建立潜在ODE的前向与反向动力学,以在紧凑潜在空间中实现T对称性。
  • 在潜在空间中以TD3+BC风格目标和T对称性正则化损失来训练Q函数与策略。
  • 利用重构与物理一致性损失学习鲁棒潜在表征(Lrec,Lfwd,Lrvs,Lds,LT-sym)。
  • 在真实生产DC(2000小时)和一个22服务器测试平台上进行评估,并与PID及其他离线/RL基线进行比较。

实验结果

研究问题

  • RQ1物理信息离线RL在有限历史数据且无仿真器的条件下,能否学习到有效且安全的DC制冷控制策略?
  • RQ2强制T对称性并使用基于GNN的动力学模型,能否提升离线RL的数据效率与OOD泛化在DC制冷中的表现?
  • RQ3在真实生产DC部署离线RL策略时,能实现的能耗节省与热安全性能如何?
  • RQ4在不同服务器负载下,控制更多的ACU对能效有何影响?
  • RQ5GNN结构与T对称性约束的消融如何影响预测误差与策略性能?

主要发现

  • 与标准PID控制器在真实生产DC中的比较,达到14–21%的能耗节省。
  • 在2000小时部署期间保持热安全,无CAT违规。
  • 长期实验显示在负载波动下,ACLF下降趋于稳定且温度场均匀性提升。
  • 测试平台与消融结果表明:结合GNN结构与T对称性约束可降低多步预测误差并提升策略性能。
  • 在数据受限的条件下,能在能效方面优于基线方法(PID、MPC、离线RL基线,以及安全离线RL),同时保持安全。

阅读本论文

在 Nubint 阅读器中打开原文,边读边就任意段落提问。

在 Nubint 中阅读本论文

本解读由 AI 根据论文原文生成,引用前请核对原文。