[论文解读] Empirical Exploration of Zone-by-zone Energy Flexibility: a Non-intrusive Load Disaggregation Approach for Commercial Buildings
本研究提出一种非侵入式负荷分解方法,为商业建筑创建‘虚拟’区域电表,从而仅通过建筑级数据即可实现区域级能源灵活性评估。研究发现,能耗最高的30%区域约占总能耗的60%和总灵活性的80%,表明可通过针对性的需求响应策略在节能与用户热舒适性之间实现平衡。
Building energy flexibility has been increasingly demonstrated as a cost-effective solution to respond to the needs of energy networks, including electric grids and district cooling and heating systems, improving the integration of intermittent renewable energy sources. Adjusting zonal temperature set-points is one of the most promising measures to unlock the energy flexibility potential of central air conditioning systems in complex commercial buildings. However, most existing studies focused on quantifying the energy flexibility on the building level since only building-level energy consumption is normally metered in commercial buildings. This study aims to investigate the impacts of temperature set-point adjustment strategies on zone-level thermal and energy performance by developing a non-intrusive data-driven load disaggregation method (i.e., a virtual zonal power meter). Three university buildings in Northern California were selected to test the proposed load disaggregation method. We found that heterogeneities of energy use and energy flexibility existed across not only buildings but also air handling units (AHUs) and zones. Moreover, a small number of zones accounted for a large amount of energy use and energy flexibility; and the most energy-intensive zones are not necessarily the most energy-flexible zones. For the three tested buildings, the top 30% most energy-intensive zones accounted for around 60% of the total energy use; and the top 30% most energy-flexible zones provided around 80% of the total energy flexibility. The proposed method enables the electric grid or district energy system operators to regard the controlled energy-flexible entities as a fleet of AHUs or zones instead of a fleet of buildings and helps unlock the possibility for targeted demand flexibility strategies that balance zone-by-zone energy reduction with zone-by-zone costs to occupants.
研究动机与目标
- 解决商业建筑中缺乏区域级能源灵活性数据的问题,因通常仅能获取建筑级计量数据。
- 开发一种可扩展、数据驱动的方法,无需侵入式传感器即可估算区域级制冷负荷与能源灵活性。
- 研究多区域商业建筑中区域、空气处理机组(AHUs)及建筑之间的能源使用与灵活性的异质性。
- 使电网运营商和建筑管理者能够设计兼顾节能与用户热舒适性成本的针对性需求响应策略。
- 评估实际温度设定点调整对区域室内空气温度的热影响。
提出的方法
- 开发一种非侵入式负荷分解模型,从建筑级计量数据中推断区域级制冷负荷,同时考虑风机功耗。
- 采用具有物理解释性、简单且可扩展的模型,将总建筑制冷负荷分解为区域级等效电负荷。
- 将该方法应用于美国加州北部的三座大学建筑,分别包含136、217和142个区域,利用历史温度设定点调整数据。
- 通过建筑级能耗数据和区域特定的温度设定点调整对虚拟区域电表进行校准。
- 通过对比预测的区域级负荷与实际热性能及温度动态,验证分解精度。
- 利用现代商业建筑中广泛部署的物联网传感器数据,实现实时、高粒度的区域级能源与热性能洞察。
实验结果
研究问题
- RQ1在何种程度上可利用非侵入式负荷分解方法,从建筑级计量数据中估算区域级能源灵活性?
- RQ2在多区域商业建筑中,能源使用与能源灵活性在区域、AHUs及建筑之间的异质性如何?
- RQ3哪些区域对总建筑能耗和能源灵活性潜力贡献最大?
- RQ4温度设定点调整对区域室内空气温度的实际热影响是什么?
- RQ5电网运营商和建筑管理者如何利用区域级灵活性洞察,设计更精准且关注用户感受的需求响应策略?
主要发现
- 所提出的非侵入式负荷分解方法成功创建了高精度的‘虚拟’区域电表,使仅基于建筑级数据即可实现区域级能源表现洞察。
- 能耗最高的30%区域约占三座测试建筑总能耗的60%。
- 能耗灵活性最高的30%区域提供了约80%的总能源灵活性,表明少数区域主导了灵活性潜力。
- 即使在同一栋建筑内,区域与AHUs之间的能源使用与灵活性差异显著,凸显热响应与电响应的强烈异质性。
- 许多区域存在过度冷却现象,室内温度频繁低于制冷设定点,表明当前控制策略存在效率问题。
- 温度设定点调整对室内空气温度的影响有限且高度异质——大多数区域的温度变化小于设定点调整幅度,且响应随时间动态变化。
阅读本论文
在 Nubint 阅读器中打开原文,边读边就任意段落提问。