[论文解读] HVAC Energy Cost Optimization for a Multi-zone Building via a Decentralized Approach

Yang Yu, Guoqiang Hu|arXiv (Cornell University)|May 21, 2019
Building Energy and Comfort OptimizationEngineering参考文献 37被引用 3
一句话总结

该论文提出了一种基于加速分布式增广拉格朗日(ADAL)算法的去中心化HVAC能效成本优化方法,用于处理多区域建筑中的热耦合与非凸动力学问题。该方法在500个区域时实现了高达19.39%的近似最优成本降低,同时相较于集中式方法及现有的去中心化方法(如DTBSS),显著提升了计算可扩展性。

ABSTRACT

It has been well acknowledged that buildings account for a large proportion of the world's energy consumption. However, the energy use of buildings, especially the heating, ventilation and air-conditioning (HVAC), is far from being efficient. There still exists a dramatic potential to save energy through improving building energy efficiency. Therefore, this paper studies the control of HVAC system for multi-zone buildings with the objective to reduce energy consumption cost while satisfying thermal comfort. In particular, the thermal couplings due to the heat transfer between the adjacent zones are incorporated in the optimization. Considering that a centralized method is generally computationally prohibitive for large buildings, an efficient decentralized approach is developed, based on the Accelerated Distributed Augmented Lagrangian (ADAL) method [1]. To evaluate the performance of the proposed method, we first compare it with a centralized method, in which the optimal solution of a small-scale problem can be obtained. We find that this decentralized approach can almost approach the optimal solution of the problem. Further, this decentralized approach is compared with the Distributed Token-Based Scheduling Strategy (DTBSS) [2]. The numeric results reveal that when the number of zones is relatively small (less than 20), the two decentralized methods can achieve a comparable performance regarding the cost of the HVAC system. However, with an increase of the number of zones in the building, the proposed decentralized approach demonstrates better performance with a considerable reduction of the total cost. Moreover, the decentralized approach proposed in this paper demonstrate better scalability with less average computation required.

研究动机与目标

  • 为解决多区域建筑中HVAC系统能耗过高的问题,特别是在HVAC能耗占建筑总能耗高达50%的热带气候地区。
  • 开发一种可扩展、计算高效的控制策略,在维持热舒适度的同时降低HVAC能耗成本。
  • 克服在具有复杂相邻区域热耦合的大规模建筑中,集中式优化在计算上不可行的问题。
  • 设计一种能够处理具有区域间传热和系统约束的非凸、非线性HVAC控制问题的去中心化方法。

提出的方法

  • 通过引入辅助变量,松弛原始的非凸、非线性HVAC优化问题,将其转化为仅含线性约束的形式。
  • 应用加速分布式增广拉格朗日(ADAL)方法,以去中心化方式求解松弛后的问题,使每个区域能够并行求解其局部子问题。
  • 每个区域通过本地信息及与邻近区域交换的对偶变量,迭代更新其本地决策变量(温度、气流、设定点)。
  • 采用启发式恢复机制,利用温度动态和耦合约束的结构特性,恢复原始问题的递归可行性。
  • 使用状态空间方程对热动态进行建模,其中包含通过系数A^ij和耦合项C^ii表示的区域间传热。
  • 通过聚合矩阵B_d^i和c_d,对全局约束(如总气流限制和热舒适度边界)进行建模,以支持分布式约束处理。

实验结果

研究问题

  • RQ1去中心化优化方法是否能在存在区域间热耦合的多区域建筑中实现接近最优的HVAC能耗成本降低?
  • RQ2对于小规模问题,所提出的去中心化方法在性能和可扩展性方面与集中式优化相比如何?
  • RQ3随着区域数量的增加,所提出方法与现有去中心化策略(如DTBSS)之间的性能差距如何?
  • RQ4在大规模HVAC系统中,该方法在保持解质量的同时,能在多大程度上降低计算负担?
  • RQ5在松弛和分布式求解之后,启发式恢复步骤是否能有效恢复原始非凸问题的递归可行性?

主要发现

  • 所提出的去中心化方法获得的解几乎是最优的,在小规模问题中与集中式方法的能耗成本极为接近。
  • 当区域数量少于20个时,所提方法与DTBSS在HVAC能耗成本上的性能差距较窄(2%–3%)。
  • 在500个区域时,所提方法相比DTBSS将HVAC能耗成本降低了19.39%,表明在大规模场景下具有更优的成本节约性能。
  • 所提方法的平均计算时间显著低于DTBSS,尤其在区域数量增加时更为明显,表明其具备更优的可扩展性。
  • 基于ADAL的去中心化方法在具有强区域间热耦合的大型复杂建筑配置中,仍能保持解的可行性与收敛性。
  • 启发式恢复步骤成功恢复了原始问题的递归可行性,确保了控制解的物理可实现性。