Skip to main content
QUICK REVIEW

[论文解读] Mitigation of Structural Harmonic Instability in Virtual Admittance-Based Grid-Forming Inverters via Mimicking Skin Effect

Jaekeun Lee, Jae-Jung Jung|arXiv (Cornell University)|Feb 4, 2026
Microgrid Control and OptimizationEngineering被引用 0
一句话总结

本文揭示了在虚拟导纳-电流控制(VA-CC)中的时延无关谐波不稳定性,源于VA与滤波器之间的非被动耦合,并提出并联虚拟电阻以模拟皮肤效应,从而在不改变CC或VFF的前提下改善被动性与稳定性。实验结果证实所提方法在相同并网条件下相对于传统VA-CC具有更强鲁棒性。

ABSTRACT

The virtual admittance-current controller (VA-CC) scheme is widely employed to emulate an equivalent inductance in front of the internal voltage source of grid-forming inverters. However, recent studies have reported harmonic instabilities associated with VA-CC, motivating the need for a more physically interpretable understanding of their origin. This letter identifies a delay-independent structural mechanism of harmonic instability in the VA-CC scheme, wherein the interaction between the filter and virtual inductances introduces a non-passive second-order transfer-function term exhibiting negative resistance. To address this issue, a simple yet effective modification is proposed by integrating a parallel virtual resistor into the VA structure. This reconfiguration enhances the passivity of VA-CC scheme across the harmonic range by mimicking the skin effect which augments damping in high-frequency range, without altering the wellestablished current controller or voltage feedforward control. Experimental results validate that the proposed method achieves robust harmonic stability, whereas the conventional approach fails under identical grid conditions.

研究动机与目标

  • Identify the structural mechanism causing harmonic instability in VA-CC.
  • Provide a physically interpretable explanation for non-passivity in the harmonic range.
  • Propose a VA redesign with a parallel virtual resistor that preserves CC and VFF.
  • Validate stability improvements experimentally under identical grid conditions.

提出的方法

  • Derive the equivalent output impedance Z_eq(s) and show a non-passive second-order term. Analyze the origin of negative resistance from s^2 L_f L_v / K_cc,p in the harmonic range.
  • Introduce a parallel virtual resistor in the VA structure and derive Y_v,prop(s). Show that Y_v,prop(jω1) matches the desired fundamental inductance and resistance, while Y_v,prop(jω) becomes resistive at high frequencies. Compare passivity of Z_eq(s) for conventional vs proposed VA across frequencies (with and without delay). Provide experimental setup and parameter values to validate stability improvements.

实验结果

研究问题

  • RQ1What causes harmonic instability in VA-CC for grid-forming inverters?
  • RQ2Can a VA redesign preserve traditional CC and VFF while stabilizing harmonics?
  • RQ3Does mimicking the skin effect via a parallel virtual resistor improve passivity and stability across the harmonic range?
  • RQ4Do experimental results corroborate the theoretical passivity enhancement and stability under real grid conditions?

主要发现

  • Conventional VA-CC introduces a non-passive second-order term in Z_eq(s) that can create negative resistance in the harmonic range.
  • The proposed VA with a parallel virtual resistor yields a passive Z_eq(s) across the frequency spectrum, improving harmonic stability.
  • The parallel virtual resistor makes 1/Y_v(s) effectively resistive at high frequencies, enhancing passivity without changing CC or VFF.
  • Experimental results show stable operation with the proposed VA and harmonic instability when the conventional VA is used under identical grid conditions.
  • FFT analysis demonstrates a dominant unstable harmonic around 348 Hz when using the conventional VA, aligning with the predicted instability region.

阅读本论文

在 Nubint 阅读器中打开原文,边读边就任意段落提问。

在 Nubint 中阅读本论文

本解读由 AI 根据论文原文生成,引用前请核对原文。