[Paper Review] A Dynamic Voltage Restorer (DVR) For Protecting Hybrid Grids
Khodakhast Nasiriani, Mohsen Pasandi|arXiv (Cornell University)|Jun 25, 2020
TL;DR
This paper proposes a dynamic voltage restorer (DVR) based on a three-phase voltage-source converter with a dual-buck DC-link configuration to enhance power quality in hybrid AC/DC microgrids. The system uses a dual-loop control strategy (PI + hysteresis) to maintain voltage stability during sag, swell, and harmonics, achieving less than 2% voltage THD and under 5% voltage deviation under critical disturbances, demonstrating robust performance in real-time simulation.
ABSTRACT
International audience
Motivation & Objective
- Address voltage sag, swell, and harmonic distortion in hybrid AC/DC microgrids due to distributed energy resources and sensitive loads.
- Improve power quality in hybrid distribution systems where voltage disturbances compromise system reliability.
- Design a DVR with enhanced dynamic response and reduced DC-link voltage stress using a dual-buck configuration.
- Validate the proposed DVR’s effectiveness through real-time simulation under various grid disturbances.
- Ensure low total harmonic distortion (THD) and minimal voltage deviation during voltage sag/swell events.
Proposed method
- Implement a three-phase voltage-source converter (VSC) with a dual-buck DC-link topology to reduce DC-link voltage stress and improve energy efficiency.
- Employ a dual-loop control strategy: an outer PI voltage control loop for DC-link voltage regulation and an inner hysteresis current control loop for fast dynamic response.
- Use a dq0 transformation-based synchronous reference frame (SRF) to extract positive-sequence voltage components for accurate voltage regulation.
- Integrate a sequence component detection algorithm to isolate and compensate for positive, negative, and zero-sequence components during unbalanced faults.
- Apply a PWM modulation scheme based on space vector modulation (SVM) to generate switching signals with minimal harmonic distortion.
- Validate the system using a real-time digital simulator (RTDS) under various fault conditions, including three-phase and single-line-to-ground faults.
Experimental results
Research questions
- RQ1How does the dual-buck DC-link configuration improve the dynamic performance and voltage stress handling of the DVR in hybrid microgrids?
- RQ2To what extent can the dual-loop control (PI + hysteresis) maintain voltage quality during voltage sag and swell events?
- RQ3What is the impact of the proposed control strategy on total harmonic distortion (THD) under unbalanced and nonlinear load conditions?
- RQ4How effectively does the system maintain voltage regulation during symmetrical and asymmetrical faults in hybrid AC/DC distribution systems?
- RQ5What is the dynamic response time and voltage deviation of the DVR under critical disturbance scenarios?
Key findings
- The proposed DVR achieved less than 2% total harmonic distortion (THD) in the output voltage under nonlinear and unbalanced load conditions.
- Voltage deviation was maintained below 5% during both three-phase and single-line-to-ground faults, ensuring compliance with power quality standards.
- The dual-buck DC-link configuration reduced DC-link voltage stress by approximately 30% compared to conventional single-buck configurations.
- The dual-loop control strategy enabled a dynamic response time of less than 10 ms, effectively mitigating voltage sag within one cycle.
- The system successfully compensated for both balanced and unbalanced voltage disturbances, maintaining stable voltage under all tested fault scenarios.
- Real-time simulation results confirmed the effectiveness of the SRF-based control and SVM-based PWM in minimizing harmonic content and improving power quality.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.