TL;DR

This paper proposes a state-aware sensor selection strategy for voltage regulation in smart grids using a hybrid dynamical system model, combining Kalman filtering for state estimation and LQR control for voltage adjustment. By applying a sliding window algorithm to optimize sensor querying order, the method reduces system cost by 40% compared to round-robin polling, achieving faster convergence and smoother voltage transitions.

ABSTRACT

The increasing availability of distributed energy resources (DERs) and sensors in smart grid, as well as overlaying communication network, provides substantial potential benefits for improving the power system's reliability. In this paper, the problem of sensor selection is studied for the MAC layer design of wireless sensor networks for regulating the voltages in smart grid. The framework of hybrid dynamical system is proposed, using Kalman filter for voltage state estimation and LQR feedback control for voltage adjustment. The approach to obtain the optimal sensor selection sequence is studied. A sub- optimal sequence is obtained by applying the sliding window algorithm. Simulation results show that the proposed sensor selection strategy achieves a 40% performance gain over the baseline algorithm of the round-robin sensor polling.

Motivation & Objective

  • Address the challenge of efficient voltage regulation in smart grids with increasing distributed energy resources (DERs) and sensor networks.
  • Improve system reliability and performance by optimizing sensor selection in wireless sensor networks with shared communication channels.
  • Develop a communication protocol at the MAC layer that adapts sensor reporting based on real-time system states rather than using fixed polling schedules.
  • Minimize overall system cost by jointly optimizing sensor selection, state estimation, and control actions in a hybrid dynamical system framework.

Proposed method

  • Model the smart grid as a hybrid dynamical system, where continuous dynamics represent power system evolution and discrete switching corresponds to sensor selection.
  • Use a Kalman filter to estimate voltage states based on partial sensor measurements, with process and measurement noise modeled as zero-mean Gaussian processes.
  • Apply Linear Quadratic Regulator (LQR) control to compute optimal DER adjustments based on estimated voltage states.
  • Formulate the sensor selection problem as a mode-switching optimization to minimize a cost function combining state deviation and control effort.
  • Implement a sub-optimal solution using a sliding window algorithm that selects the next sensor based on predicted system performance over a finite horizon.
  • Integrate sensor noise covariance and system dynamics to prioritize sensors with higher information value, especially those with higher measurement uncertainty.

Experimental results

Research questions

  • RQ1How can sensor selection in wireless sensor networks be optimized to improve voltage regulation performance in smart grids?
  • RQ2What is the impact of state-aware sensor scheduling compared to fixed round-robin polling on system cost and convergence speed?
  • RQ3How does the integration of Kalman filtering and LQR control affect the accuracy and stability of voltage state estimation and regulation?
  • RQ4To what extent can a sliding window-based sensor selection algorithm reduce system cost while maintaining computational efficiency?

Key findings

  • The proposed sensor selection strategy reduces system cost by approximately 40% compared to the baseline round-robin polling method.
  • Voltage deviation converges to zero significantly faster under the proposed strategy, with full stabilization achieved by time step $ k = 30 $, compared to continued deviation beyond $ k = 40 $ under round-robin.
  • The proposed method achieves lower voltage state estimation error, enabling more accurate and timely control actions by the DERs.
  • Sensor 3, despite having the highest measurement noise, is allocated 45% of channel access due to its high information value in the overall system state estimation.
  • The voltage state trajectory under the proposed strategy exhibits smoother transitions, reducing fluctuations and improving power quality.
  • Sensor 1 receives 35% of channel access and Sensor 2 20%, reflecting their relative contributions to reducing combined process and measurement noise in the estimation process.