[Paper Review] Towards Phase Balancing using Energy Storage
This paper proposes using small-scale energy storage at the end-of-feeder locations to mitigate three-phase network unbalance caused by single-phase distributed generation (DG) and electric vehicle (EV) charging. Using OpenDSS-based simulations on real-world case studies from Madeira and Pasadena, it demonstrates that even 3kW storage units can significantly reduce neutral and phase losses, voltage unbalance factor (VUF), and voltage deviations—particularly when placed at the feeder's end—outperforming substation-level storage by a wide margin.
Ad-hoc growth of single-phase-connected distributed energy resources, such as solar generation and electric vehicles, can lead to network unbalance with negative consequences on the quality and efficiency of electricity supply. Case-studies are presented for a substation in Madeira, Portugal and an EV charging facility in Pasadena, California. These case studies show that phase imbalance can happen due to a large amount of distributed generation (DG) and electric vehicle (EV) integration. We conducted stylized load-flow analysis on a radial distribution network using an openDSS-based simulator to understand such negative effects of phase imbalance on neutral and phase conductor losses, and in voltage drop/rise. We evaluate the integration of storage in the distribution network as a possible solution for mitigating effects caused by imbalance. We present control architectures of storage operation for phase balancing. Numerically we show that relatively small-sized storage (compared to unbalance magnitude) can significantly reduce network imbalance. We identify the end node of the feeder as the best location to install storage.
Motivation & Objective
- Address the growing problem of three-phase network unbalance due to uncoordinated single-phase distributed energy resources (DG) and electric vehicles (EVs).
- Investigate the impact of unbalanced loading and generation on key power quality and efficiency metrics in radial distribution networks.
- Evaluate energy storage as a control mechanism for phase balancing, focusing on minimizing losses and voltage deviations.
- Identify optimal storage placement and control architecture to maximize unbalance mitigation with minimal storage capacity.
- Demonstrate that small-sized storage can achieve significant improvements in network performance metrics despite unbalance magnitude being much larger.
Proposed method
- Conducted stylized load-flow analysis on a radial distribution network using the OpenDSS simulator to model unbalanced three-phase systems with single-phase DG and EV loads.
- Simulated two real-world case studies: a substation in Madeira, Portugal, and an EV charging facility in Pasadena, California, to assess real-world unbalance effects.
- Defined and computed key metrics: voltage unbalance factor (VUF), neutral and phase conductor losses, and voltage drop/rise across the network.
- Proposed and evaluated three storage control architectures: substation-level, end-of-feeder, and flexible phase-switching with load shifting.
- Used a 3kW battery storage unit in simulations to assess impact on unbalance metrics, comparing performance across different locations and control strategies.
- Analyzed sensitivity of metrics to phase balancing versus load shifting, showing phase control dominates over temporal load shifting in effectiveness.
Experimental results
Research questions
- RQ1How does the placement of single-phase DG and EV charging affect phase imbalance in radial distribution networks?
- RQ2To what extent can small-sized energy storage (relative to imbalance magnitude) reduce neutral and phase losses, voltage unbalance, and voltage deviations?
- RQ3Which storage control architecture—substation-level, end-of-feeder, or flexible phase-switching—provides the most effective mitigation of network unbalance?
- RQ4How does the sensitivity of unbalance metrics compare between phase balancing and load shifting in time?
- RQ5What is the impact of network topology (e.g., radial, long feeder) on the effectiveness of storage-based phase balancing?
Key findings
- Storage located at the end of the feeder (N5) reduced the maximum voltage unbalance factor (VUF) from 1.30% (no storage, unbalanced) to 0.87% under Architecture 1, a 33% reduction.
- Neutral losses were reduced from 3.29 kWh (no storage) to 1.78 kWh with 3kW storage at the feeder end under Architecture 1, a 45.3% reduction.
- The maximum voltage drop/rise was reduced from 8.30% (no storage) to 5.98% with end-of-feeder storage under Architecture 1, a 27.7% improvement.
- Architecture 1 (phase-balancing only) outperformed Architecture 2 (phase-switching with load shifting) in all metrics, indicating phase control is more effective than load shifting.
- Substation-level storage (N0) had minimal impact on VUF and losses, reducing VUF only to 1.26%—a 4.6% improvement over no storage, showing poor effectiveness.
- Even without load shifting, phase balancing with 3kW storage reduced VUF to 1.01% (from 1.30%), demonstrating that phase control dominates over temporal load management in performance.
Read this paper