[Paper Review] What can transmission do for a fully renewable Europe?
This study investigates how high-voltage transmission can reduce mismatches between variable renewable energy (VRES) generation and electricity demand across Europe. Using weather-driven modeling and a DC power flow transmission framework, it finds that transmission can reduce balancing energy needs by up to 40% in a fully renewable Europe, with 90% of this benefit achievable by quadrupling current transmission capacity. Position and load size are key determinants of national import/export potential.
Our research is centred around the question how to best integrate the variable renewable energy sources (VRES), wind power and solar photovoltaics, into the European electricity grid. The future electricity supply will be based to a large extend on these fluctuating resources. We have conducted a study, extrapolating national historical and targeted wind and solar power penetrations in Europe up to 100% VRES (R.A. Rodriguez et al, Renewable Energy 63, p. 467, Mar 2014 and S. Becker et al, Energy 64, p. 404, Jan 2014). A high share of VRES means large fluctuations in the generation, causing overproduction and deficits. One way to reduce such mismatches is power transmission spatially smoothing out the fluctuations. This has the potential to reduce the remaining shortages by sharing the surplus production of others. We find that shortages can at maximum be reduced by 40% in the hypothetical case of unlimited transmission capacities across all of Europe. A more realistic extension of the transmission grid, roughly quadrupling today's installation, turns out to be sufficient to harvest 90% of this potential benefit. Finally, the import and export of single countries is investigated. We conclude that a country's load size as well as its position in the network are the determining factors for its import/export opportunities.
Motivation & Objective
- To assess the technical potential of power transmission to reduce mismatches between variable renewable energy (VRES) generation and load in Europe.
- To evaluate how transmission capacity expansion affects national import and export opportunities for electricity.
- To identify efficient reinforcement strategies for the European transmission grid to maximize spatial smoothing benefits.
- To examine the time evolution of mismatch distributions under different transmission scenarios.
Proposed method
- Weather-driven modeling of wind and solar PV generation using eight years of hourly historical weather data, aggregated to national level.
- Normalization of generation and load data to a common mean, enabling extrapolation to 100% VRES scenarios via logistic fitting.
- Definition of the mismatch between renewable generation and load using a formula that incorporates country-specific wind/solar shares and scaling factors.
- Application of a generalized DC power flow model to simulate power exchange across European countries, enabling spatial smoothing of generation fluctuations.
- Simulation of transmission benefits under two scenarios: today’s transmission capacities and a hypothetical 90% benefit scenario from expanded grid capacity.
- Use of quantile capacity interpolation to guide efficient grid reinforcement, prioritizing links that maximize national and regional balancing benefits.
Experimental results
Research questions
- RQ1To what extent can transmission reduce the total energy mismatch between variable renewable generation and electricity demand in a fully renewable Europe?
- RQ2How do national load size and geographic position in the transmission network influence a country’s ability to import or export surplus renewable electricity?
- RQ3What is the optimal strategy for reinforcing the European transmission grid to maximize the benefits of spatial smoothing?
- RQ4How does the distribution of mismatch events evolve over time under different transmission capacity scenarios?
- RQ5To what extent can transmission mitigate large-scale mismatch events, particularly extreme deficits and surpluses?
Key findings
- Transmission can reduce the total balancing energy required in a fully renewable Europe by up to 40%, primarily by smoothing out the bulk of mismatch events.
- A realistic expansion of transmission capacity—approximately quadrupling today’s levels—can capture 90% of the maximum potential benefit from transmission.
- The remaining 60% of balancing energy cannot be mitigated by transmission alone, indicating that additional measures such as storage or demand-side management are essential.
- Countries with larger loads, such as Germany, benefit less from transmission than smaller countries like Denmark, due to lower export potential relative to their own demand.
- Geographic position significantly affects trade potential: countries like Spain benefit less from transmission expansion than central or northern European countries like Denmark.
- Transmission is most effective at reducing moderate mismatch events; large surplus and deficit events remain largely unaffected, suggesting that spatial smoothing alone cannot resolve extreme imbalances.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.
Read this paper on NubintThis review was generated by AI from the original paper. Please check the paper before citing it.