[Paper Review] A benchmark for data-based office modeling: challenges related to CO$_2$ dynamics
This paper presents a synthetic benchmark dataset of CO2 dynamics in a simulated office environment using IDA-ICE, focusing on blind system identification of occupancy from CO2 concentration. It evaluates two data-based modeling approaches—overparameterization and kernel-based methods—demonstrating that open windows significantly degrade occupancy estimation accuracy, with CO2 fit dropping to 80.3–87.2% and occupancy fit to 37.9–67.1% under open-window conditions.
This paper describes a benchmark consisting of a set of synthetic measurements relative to an office environment simulated with the software IDA-ICE. The simulated environment reproduces a laboratory at the KTH-EES Smart Building, equipped with a building management system. The data set contains records collected over a period of several days. The signals to CO$_2$ concentration, mechanical ventilation airflows, air infiltrations and occupancy. Information on door and window opening is also available. This benchmark is intended for testing data-based modeling techniques. The ultimate goal is the development of models to improve the forecast and control of environmental variables. Among the numerous challenges related to this framework, we point out the problem of occupancy estimation using information on CO$_2$ concentration. This can be seen as a blind identification problem. For benchmarking purposes, we present two different identification approaches: a baseline overparametrization method and a kernel-based method.
Motivation & Objective
- To develop a standardized benchmark dataset for data-based modeling of indoor environmental dynamics in office buildings.
- To address the challenge of blind identification of occupancy from CO2 concentration measurements, without access to direct occupancy data.
- To evaluate and compare the performance of different system identification techniques under realistic office conditions, including variable occupancy and window opening.
- To highlight the impact of unmodeled dynamics—particularly open windows—on the accuracy of occupancy and CO2 modeling.
- To support the development of model predictive control (MPC) strategies for energy-efficient indoor climate management.
Proposed method
- Simulates a real laboratory at KTH using IDA-ICE software over a one-week period with variable occupancy, mechanical ventilation, and window/door states.
- Generates synthetic data for CO2 concentration, mechanical ventilation flow, infiltration, and occupancy, with 3-minute sampling resolution.
- Applies a blind identification framework where occupancy is estimated solely from CO2 measurements, treating it as a system identification problem with unknown inputs.
- Uses two identification methods: a baseline overparameterization technique and a kernel-based method with stable spline kernel for regularization.
- Evaluates model performance using two fit metrics: CO2 signal prediction fit and occupancy signal reconstruction fit.
- Performs daily identification on weekdays (Monday–Friday), excluding weekends, and computes average performance across days for each scenario.
Experimental results
Research questions
- RQ1How accurately can occupancy be estimated from CO2 concentration data when no direct occupancy measurements are available?
- RQ2How do unmodeled dynamics such as window opening affect the performance of data-based models in estimating occupancy and CO2 levels?
- RQ3What is the comparative performance of overparameterization versus kernel-based methods in blind system identification of office CO2 dynamics?
- RQ4To what extent does the presence of variable ventilation and infiltration impact the reliability of CO2-based occupancy estimation?
- RQ5Can the benchmark dataset support the development and validation of model predictive control strategies for indoor environmental quality?
Key findings
- The kernel-based method achieves CO2 prediction fits between 89.7% and 98.4% when windows are closed, indicating strong model accuracy under controlled conditions.
- When windows are open, CO2 prediction fits drop to 80.3–87.2%, showing that unmodeled infiltration significantly degrades model performance.
- Occupancy estimation performance drops substantially under open-window conditions, with fits ranging from 37.9% to 67.1%, indicating poor reconstruction of occupancy patterns.
- The overparameterization method fails to capture CO2 dynamics or reconstruct occupancy, yielding negative fit scores, and is therefore ineffective for this task.
- The benchmark reveals that window opening is a critical, often neglected factor in CO2-based occupancy estimation, severely impacting model accuracy.
- The dataset is effective for evaluating system identification algorithms and supports future research in smart building control and energy efficiency.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.