Skip to main content
QUICK REVIEW

[Paper Review] Analysis of November 21, 2021, Kaua`i Island Power System 18-20 Hz Oscillations

Shuan Dong, Bin Wang|arXiv (Cornell University)|Jan 13, 2023
NMR spectroscopy and applicationsPhysics and Astronomy7 citations
TL;DR

The paper identifies sources of an 18–20 Hz system-wide oscillation on Kaua‘i caused by inverter-based resources after a plant trip, recreates it with EMT models, and proposes two mitigation methods validated by simulations.

ABSTRACT

This letter discusses the 18-20 Hz oscillation event at 05:30 am on November 21, 2021, in Kaua`i's power system following the trip of an oil power plant. As far as the authors are aware, this is the first report of a transmission system-wide subsynchronous oscillation driven by inverter-based resources (though the system in question is relatively small). In this letter, we leverage two data-based methods-the dissipating energy flow method and the sub/super-synchronous power flow method-to locate the sources of the oscillation. Also, we build an electromagnetic transient model of the Kaua`i power system and replay the 18-20 Hz oscillation. Finally, we propose two mitigation methods and validate their effectiveness via numerical simulation.

Motivation & Objective

  • Identify the sources of the 18–20 Hz oscillations observed on Kaua‘i Island after a contingency event.
  • Recreate the oscillation using an EMT power system model to validate understanding of dynamics.
  • Develop and validate mitigation strategies to suppress the oscillation.
  • Assess the effectiveness of inverter-based resource controls in damping system-wide subsynchronous oscillations.
  • Suggest directions for future work including grid-forming controls and hardware-in-the-loop validation.

Proposed method

  • Use two measurement-based methods (dissipating energy flow and sub/super-synchronous power flow) to locate oscillation sources from PMU and high-rate PoW data.
  • Build an EMT (PSCAD) model of the Kaua‘i system with revised KIUC data and vendor models for IBRs to replay the 18–20 Hz event.
  • Perform Prony analysis on IBR responses to identify mode shapes and relative phasing.
  • Conduct parameter sensitivity studies in the EMT model to evaluate mitigation options.
  • Validate EMT model accuracy by comparing simulated and recorded frequency and power responses (FFT spectra and time-domain traces).
  • Propose two mitigation approaches: (1) adjust inverter-level P/f droop constant, (2) reduce PLL proportional gains in IBRs, and test their impact via EMT simulations.

Experimental results

Research questions

  • RQ1Where do the 18–20 Hz oscillations originate after the plant A trip on Kaua‘i Island?
  • RQ2Can an EMT model replicate the observed oscillations and mode shapes to validate understanding of the dynamics?
  • RQ3Do targeted changes to inverter controls mitigate the 18–20 Hz oscillations effectively in simulations?
  • RQ4What is the role of grid-following versus grid-forming inverter controls in damping such oscillations on a small islanded grid?

Key findings

  • Both DEF and sub/super-synchronous power flow analyses identify IBR1 and IBR2 as the oscillation sources.
  • EMT simulations reproduce the 18–20 Hz oscillations and show IBR1 and IBR2 oscillating against IBR3 and IBR4, consistent with measurements.
  • The IBRs’ energy exchanges and mode shapes during the event match between measurements and EMT results.
  • Two mitigation options are effective in simulations: increasing the P/f droop from 3.0% to 4.0%, and reducing PLL gains from 0.15 to 0.10, both of which suppress the 18–20 Hz oscillations.
  • KIUC subsequently converted IBR1 from grid-following to grid-forming, observed to mitigate the oscillations.
  • Acknowledges potential for grid-forming IBR controls as a mitigation path and the value of further validation with hardware-in-the-loop or field tests.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.