Skip to main content
QUICK REVIEW

[Paper Review] Analyzing and Mitigating the Impacts of GMD and EMP Events on the Electrical Grid with PowerModelsGMD.jl

Ádám Máté, Arthur K. Barnes|arXiv (Cornell University)|Jan 13, 2021
Lightning and Electromagnetic PhenomenaPhysics and Astronomy7 citations
TL;DR

This paper introduces PowerModelsGMD.jl, an open-source Julia-based framework for modeling and mitigating geomagnetically induced currents (GICs) in power systems due to GMD and EMP events. It enables time-extended optimal power flow with transformer thermal constraints, demonstrating effective mitigation via line switching that keeps transformer hot-spot temperatures below 280°C during a 6-hour simulated event.

ABSTRACT

Geomagnetic disturbances and E3 high-altitude electromagnetic pulse events pose a substantial threat to the electrical grid by adversely impacting and damaging high-voltage transmission networks and equipment. To evaluate the risks and mitigate the potential effects of these hazards, this work proposes PowerModelsGMD.jl (abbr. PMsGMD). PMsGMD is an open-source Julia package that solves for quasi-dc line flow and ac power flow problems in a system subjected to geomagnetically induced currents. Unlike commercially available software solutions, it is extensible and applicable to a variety of problems. The flexibility of this framework is demonstrated by applying it to the problem of identifying mitigation strategies via line switching for a time-extended transformer heating problem. An overview of PMsGMD is presented in this paper: introduction to its design, validation of its implementation, demonstration of its performance and effectiveness, and a description of how it may be applied to aid system-operation decisions.

Motivation & Objective

  • To address the growing threat of geomagnetic disturbances (GMDs) and high-altitude EMP (HEMP) events on high-voltage transmission systems.
  • To develop a flexible, extensible, and open-source tool for simulating GICs and their impacts on power system components, particularly transformers.
  • To enable time-extended optimal power flow for GIC mitigation, focusing on transformer thermal heating and operational decision-making.
  • To validate the framework on realistic test systems and demonstrate its scalability and effectiveness in real-time and planning scenarios.

Proposed method

  • Extends the PowerModels.jl framework in Julia to model quasi-DC line flow and AC power flow under GIC injection.
  • Introduces a time-extended formulation that captures dynamic GIC evolution and cumulative thermal stress on transformers.
  • Uses JuMP for mathematical optimization to solve optimal transmission switching (OTS) problems under GIC constraints.
  • Models GIC injection via equivalent neutral current injection at transformer wye-bus connections based on spatial electric field and ground resistivity.
  • Applies a thermal aging model to estimate hot-spot temperature rise in transformers due to GIC-induced losses.
  • Employs a nonlinear solver (Gurobi) to solve the time-extended optimal power flow problem with thermal limits and line switching decisions.

Experimental results

Research questions

  • RQ1How can GICs be accurately modeled in transmission systems under time-varying geomagnetic and EMP electric fields?
  • RQ2Can an open-source framework effectively simulate GIC-induced thermal stress on large power transformers over extended durations?
  • RQ3What line switching strategies minimize transformer hot-spot temperature rise during a GMD/HEMP event?
  • RQ4How scalable and computationally efficient is the proposed framework for real-time and planning applications?
  • RQ5Can the framework support advanced mitigation strategies such as optimal GIC blocker placement or harmonic load flow?

Key findings

  • The PMsGMD framework successfully simulates GIC flow and transformer thermal response under a 6-hour time-varying electric field, with field magnitude increasing from 0 to 3.2 V/km over 3 hours and decreasing back to zero.
  • The optimization-based mitigation strategy reduced GIC flow through critical transformers by opening specific lines, including the longest East-West line (4-6-1) and one line in the 4-5 corridor.
  • Transformer 12-13-1’s hot-spot temperature was kept below the 280°C instantaneous thermal limit throughout the simulation, validating the effectiveness of the mitigation strategy.
  • The mitigation strategy computation took 21 seconds on a standard desktop system, demonstrating feasibility for near real-time operational use.
  • The framework is extensible and supports future extensions such as harmonic load flow, scenario-based optimization, and optimal GIC blocker placement.
  • Validation on a 11-bus system confirmed the correctness of the implementation and the accuracy of the thermal modeling under dynamic GIC conditions.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.