[Paper Review] Control-mode as a Grid Service in Software-defined Power Grids: GFL vs GFM

Guoxuan Cui, Zhongda Chu|arXiv (Cornell University)|Jul 28, 2023
Microgrid Control and OptimizationEngineering3 citations
TL;DR

This paper proposes a dynamic, software-defined optimization framework that determines the optimal real-time allocation of Grid-Forming (GFM) and Grid-Following (GFL) converters in power systems to balance grid strength enhancement and operational cost. By jointly considering active/reactive power reserves and small-signal stability constraints, the framework minimizes system costs while ensuring stability, with case studies showing significant cost reductions and adaptive GFM penetration levels based on wind power and location.

ABSTRACT

In power systems with high penetration of power electronics, grid-forming control is proposed to replace traditional Grid-Following Converter (GFL) in order to improve the overall system strength and resist small-signal instability in weak grids by directly forming the terminal voltage. However, sufficient headroom of both active and reactive power must be made available for Grid-Forming Converter (GFM) to operate, potentially leading to sub-optimal operation in steady states. This presents a new research problem to optimally allocate between GFM and GFL to balance the ability of GFMs to improve the grid strength and the potential economic loss resulting from reserved headroom. An optimization framework under software-defined grids is proposed, for the first time, to dynamically determine the optimal allocation of GFMs and GFLs in power systems at each time step of system scheduling according to system conditions, which ensures both system stability and minimum operational cost. To achieve this, the system scheduling model is expanded to simultaneously consider the constraints related to active and reactive power reserves for GFMs, as well as the system level stability. Case studies conducted on the modified IEEE 30-bus system demonstrate significant economic benefits in that the optimal proportion of GFMs in the power system can be dynamically determined while ensuring power reserve and grid stability constraints.

Motivation & Objective

  • Address the trade-off between enhanced grid strength from GFM converters and the economic loss due to reserved active/reactive power headroom in steady-state operation.
  • Overcome the limitation of static, planning-level GFM allocation by enabling time-varying, system-condition-dependent control mode selection.
  • Ensure system stability by incorporating small-signal stability constraints and power reserve requirements into the scheduling framework.
  • Minimize operational cost in power systems with high renewable penetration by dynamically optimizing the proportion of GFM and GFL converters.
  • Integrate grid-forming capabilities into a software-defined grid architecture to enable real-time, adaptive control mode allocation.

Proposed method

  • Formulate a unit commitment-based optimization model that includes constraints for active and reactive power reserves required by GFM converters.
  • Extend the system scheduling model to include small-signal stability constraints derived from the grid strength and system dynamics.
  • Introduce a dynamic control mode allocation variable (αj) for each converter bus to represent the proportion of GFM operation at each time step.
  • Use a mixed-integer linear programming (MILP) formulation to solve the optimization problem under varying system conditions, including wind power availability and load demand.
  • Incorporate grid strength metrics and small-signal stability criteria to prevent instability in weak or strong grid conditions.
  • Implement the framework in a modified IEEE 30-bus system to evaluate performance under different wind penetration levels and locations.

Experimental results

Research questions

  • RQ1How does the optimal allocation of GFM and GFL converters vary with changing wind power penetration levels in a power system?
  • RQ2What is the impact of converter location on the optimal GFM penetration level and system stability?
  • RQ3To what extent can dynamic GFM allocation reduce system operational costs while maintaining power reserves and stability?
  • RQ4How does the inclusion of small-signal stability constraints affect the optimal GFM allocation and system cost?
  • RQ5Can a software-defined grid architecture enable real-time, adaptive control mode selection between GFM and GFL to balance stability and economic efficiency?

Key findings

  • The optimal GFM penetration level increases with higher wind power penetration, rising from 0.4–0.6 at 450 MW to 0.6–0.9 at 750 MW in one wind farm.
  • Wind farms located in stronger system strength positions (e.g., Wind Farm 1) achieve higher optimal GFM penetration levels than those in weaker locations (e.g., Wind Farm 2).
  • System operational cost is significantly reduced when GFM is used (red curve in Fig. 8), with the largest cost reduction occurring at intermediate wind penetration (~600 MW).
  • The cost difference between systems with and without small-signal stability constraints is largest at intermediate wind levels, indicating that instability risk is most acute there.
  • The framework enables dynamic GFM allocation that avoids curtailment losses by utilizing reserved headroom for grid support, reducing economic inefficiency.
  • The optimal solution avoids assigning GFM to all wind farms at once, with lower density of αj = 0 solutions at high wind penetration, indicating increased GFM utilization.