Skip to main content
QUICK REVIEW

[Paper Review] Degradation-aware data-enabled predictive control of energy hubs

Varsha Behrunani, Marta Zagórowska|arXiv (Cornell University)|Jul 4, 2023
Building Energy and Comfort OptimizationEngineering1 citations
TL;DR

This paper proposes a degradation-aware data-enabled predictive control (DeePC) framework for energy hubs in buildings, using historical input-output data to optimize battery and heat pump operation without explicit system models. By incorporating battery degradation dynamics into the control optimization, DeePC reduces battery ageing by over 50% and improves comfort constraint satisfaction compared to a rule-based controller, while maintaining similar operational costs.

ABSTRACT

Mitigating the energy use in buildings, together with satisfaction of comfort requirements are the main objectives of efficient building control systems. Augmenting building energy systems with batteries can improve the energy use of a building, while posing the challenge of considering battery degradation during control operation. We demonstrate the performance of a data-enabled predictive control (DeePC) approach applied to a single multi-zone building and an energy hub comprising an electric heat pump and a battery. In a comparison with a standard rule-based controller, results demonstrate that the performance of DeePC is superior in terms of satisfaction of comfort constraints without increasing grid power consumption. Moreover, DeePC achieved two-fold decrease in battery degradation over one year, as compared to a rule-based controller.

Motivation & Objective

  • To develop a data-driven control strategy that accounts for battery degradation in building energy systems.
  • To reduce energy consumption and improve comfort in multi-zone buildings with integrated energy hubs.
  • To minimize battery degradation over the system's lifetime without relying on complex first-principles models.
  • To compare the performance of DeePC against a rule-based controller (RBC) in terms of energy use, comfort, and battery longevity.

Proposed method

  • DeePC uses persistently exciting input-output trajectories to construct Hankel matrices and replace system models in predictive control.
  • The optimization problem is formulated using data-based system representation via the Fundamental Lemma, ensuring trajectory feasibility.
  • Battery degradation is modeled through cycle count and capacity loss, with constraints on voltage and state-of-charge enforced in the control horizon.
  • A regularization term on the weighting vector g prevents overfitting and improves robustness.
  • The controller uses slack variables ρ to penalize comfort constraint violations, enabling soft constraints.
  • The approach integrates real-time forecasts of disturbances (e.g., weather, occupancy) and leverages low-level controller performance without modeling them.

Experimental results

Research questions

  • RQ1Can data-enabled predictive control (DeePC) effectively manage energy hubs with battery degradation while maintaining comfort and minimizing grid usage?
  • RQ2How does DeePC compare to a rule-based controller (RBC) in terms of battery ageing and constraint violations over a full year?
  • RQ3To what extent can DeePC reduce battery degradation without requiring detailed first-principles models of degradation?
  • RQ4Can DeePC maintain or improve comfort constraints while reducing grid power consumption compared to RBC?
  • RQ5How does the inclusion of battery voltage and SoC constraints in DeePC affect system longevity and performance?

Key findings

  • DeePC reduced battery ageing by a factor of two over one year, with 100 cycles compared to 200 cycles under the rule-based controller.
  • Battery capacity loss was reduced to 0.3% under DeePC, compared to 0.8% under RBC.
  • Comfort constraint violations were reduced to 2.8% of the time under DeePC, compared to 5.5% under RBC.
  • The cost of operation was comparable between DeePC (CHF 5909.8) and RBC (CHF 5961.7), with DeePC achieving 0.9% lower cost.
  • Prediction errors for room temperature were below 0.5 °C on average, and battery voltage errors remained under 0.5 V, indicating high accuracy.
  • DeePC successfully enforced voltage constraints, whereas RBC only regulated current, leading to oscillatory behaviour and accelerated degradation.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.