This study introduces a non-intrusive load disaggregation method to create 'virtual' zonal power meters for commercial buildings, enabling zone-level energy flexibility assessment from building-level data. It reveals that top 30% of zones account for ~60% of energy use and ~80% of flexibility, enabling targeted demand response strategies that balance energy savings with occupant thermal comfort.
Building energy flexibility has been increasingly demonstrated as a cost-effective solution to respond to the needs of energy networks, including electric grids and district cooling and heating systems, improving the integration of intermittent renewable energy sources. Adjusting zonal temperature set-points is one of the most promising measures to unlock the energy flexibility potential of central air conditioning systems in complex commercial buildings. However, most existing studies focused on quantifying the energy flexibility on the building level since only building-level energy consumption is normally metered in commercial buildings. This study aims to investigate the impacts of temperature set-point adjustment strategies on zone-level thermal and energy performance by developing a non-intrusive data-driven load disaggregation method (i.e., a virtual zonal power meter). Three university buildings in Northern California were selected to test the proposed load disaggregation method. We found that heterogeneities of energy use and energy flexibility existed across not only buildings but also air handling units (AHUs) and zones. Moreover, a small number of zones accounted for a large amount of energy use and energy flexibility; and the most energy-intensive zones are not necessarily the most energy-flexible zones. For the three tested buildings, the top 30% most energy-intensive zones accounted for around 60% of the total energy use; and the top 30% most energy-flexible zones provided around 80% of the total energy flexibility. The proposed method enables the electric grid or district energy system operators to regard the controlled energy-flexible entities as a fleet of AHUs or zones instead of a fleet of buildings and helps unlock the possibility for targeted demand flexibility strategies that balance zone-by-zone energy reduction with zone-by-zone costs to occupants.
Motivation & Objective
- Address the lack of zone-level energy flexibility data in commercial buildings, where only building-level metering is typically available.
- Develop a scalable, data-driven method to estimate zone-level cooling load and energy flexibility without intrusive sensors.
- Investigate the heterogeneity of energy use and flexibility across zones, air handling units (AHUs), and buildings.
- Enable grid operators and building managers to design targeted demand response strategies that balance energy savings with occupant thermal costs.
- Assess the real-world thermal impact of temperature set-point adjustments on indoor air temperature at the zone level.
Proposed method
- Developed a non-intrusive load disaggregation model to infer zone-level cooling load from building-level metered data, incorporating fan power consumption.
- Used physically interpretable, simple, and scalable models to disaggregate total building cooling load into zone-level equivalent electrical loads.
- Applied the method to three university buildings in Northern California with 136, 217, and 142 zones, respectively, using historical temperature set-point adjustment data.
- Calibrated the virtual zonal power meter using building-level energy consumption and zone-specific temperature set-point adjustments.
- Validated the disaggregation accuracy by comparing predicted zone-level loads with actual thermal performance and temperature dynamics.
- Leveraged widespread IoT sensor data in modern commercial buildings to enable high-granularity, real-time insights into zone-level energy and thermal performance.
Experimental results
Research questions
- RQ1To what extent can zone-level energy flexibility be estimated from building-level metered data using a non-intrusive load disaggregation approach?
- RQ2How heterogeneous is energy use and energy flexibility across zones, AHUs, and buildings in multi-zone commercial buildings?
- RQ3Which zones contribute the most to total building energy use and energy flexibility potential?
- RQ4What is the actual thermal impact of temperature set-point adjustments on indoor air temperature at the zone level?
- RQ5How can grid operators and building managers use zone-level flexibility insights to design more targeted and occupant-aware demand response strategies?
Key findings
- The proposed non-intrusive load disaggregation method successfully created accurate 'virtual' zonal power meters, enabling zone-level energy performance insights from building-level data.
- Top 30% of the most energy-intensive zones accounted for approximately 60% of the total building energy use across the three tested buildings.
- The top 30% of the most energy-flexible zones provided around 80% of the total energy flexibility, indicating a small subset of zones dominates flexibility potential.
- Energy use and flexibility varied significantly across zones and AHUs, even within the same building, highlighting strong heterogeneity in thermal and electrical responses.
- Over-cooling was observed in many zones, with indoor temperatures frequently falling below cooling set-points, indicating inefficiencies in current control strategies.
- The effect of temperature set-point adjustments on indoor air temperature was limited and highly heterogeneous—most zones experienced temperature changes less than the set-point adjustment, and responses varied dynamically over time.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.
Read this paper on NubintThis review was generated by AI from the original paper. Please check the paper before citing it.