[Paper Review] Numerical Study on Flow and Heat Transfer of Water and Liquid Metals Within Micro-Scale Heat Sinks for High Heat Dissipation Rate Applications

Mahyar Pourghasemi, Nima Fathi|arXiv (Cornell University)|Jun 13, 2021
Heat Transfer and OptimizationEngineering18 references6 citations
TL;DR

This numerical study investigates slip effects on flow and heat transfer in micro-scale heat sinks using water and liquid metals, demonstrating that a 2-micron slip length enhances thermal-hydraulic performance by 6%—increasing Nusselt number by 4% and reducing pumping power by 8%—compared to no-slip conditions at identical mass flow rates and inlet Reynolds numbers.

ABSTRACT

Compact and small-scale heat exchangers can handle high heat dissipation rates due to their large surface area to volume ratios. Applications involving high heat dissipation rates include, but are not limited to, compact microelectronic processing units, high power laser arrays, fuel cells, as well as fission batteries. Low maintenance cost, small size and dimensions, as well as high convective heat transfer coefficients, make micro-scale heat sinks an efficient and reliable cooling solution for applications with high heat dissipation rates. Despite these advantages, the large pressure drop that occurs within micro-scale heat sinks has restricted their utilization. Slip at the walls of microchannels has been reported to reduce friction factor up to 30%, depending on the hydraulic diameter of the microchannel. Numerical investigations are conducted to comprehensively investigate the effect of slip at walls on friction factor and Nusselt number of liquid flows in micro-scale heat sinks. At the same mass flow rate and inlet Reynolds number, obtained results suggest that slip length on the order of 2 microns enhances the overall thermalhydraulic performance of micro heat sinks by almost 6% in comparison with no-slip boundary conditions. 4% increase is observed in channel average Nusselt number while pumping power reduces by 8% in comparison with no-slip boundary condition.

Motivation & Objective

  • To evaluate the impact of wall slip on friction factor and Nusselt number in micro-scale heat sinks.
  • To compare thermal-hydraulic performance between no-slip and slip boundary conditions in microchannels.
  • To assess the performance of water and liquid metals under slip conditions for high heat dissipation applications.
  • To quantify improvements in heat transfer efficiency and pumping power reduction due to slip effects.
  • To provide design insights for compact, high-performance heat sinks in microelectronics and high-power systems.

Proposed method

  • Conducted 3D numerical simulations of laminar flow and heat transfer in micro-scale heat sinks.
  • Applied slip boundary conditions with slip lengths up to 2 microns at channel walls.
  • Used the Navier-Stokes equations with modified no-slip boundary conditions to model slip effects.
  • Simulated both water and liquid metals (e.g., gallium-based alloys) under identical inlet Reynolds numbers and mass flow rates.
  • Calculated key performance indicators: friction factor, Nusselt number, and pumping power.
  • Compared results between no-slip and slip boundary conditions to evaluate performance gains.

Experimental results

Research questions

  • RQ1How does wall slip influence the friction factor in micro-scale heat sinks?
  • RQ2What is the effect of slip length on the Nusselt number and heat transfer enhancement?
  • RQ3To what extent does slip reduce pumping power requirements in microchannel heat sinks?
  • RQ4How do the thermal-hydraulic performance metrics compare between water and liquid metals under slip conditions?
  • RQ5Can slip boundary conditions improve the overall thermal-hydraulic performance index in high-heat-flux applications?

Key findings

  • A slip length of 2 microns increases the overall thermal-hydraulic performance by approximately 6% compared to no-slip conditions.
  • The channel-averaged Nusselt number increases by 4% under slip conditions at the same mass flow rate and inlet Reynolds number.
  • Pumping power is reduced by 8% when slip length is set to 2 microns, indicating lower energy consumption.
  • Slip reduces the friction factor by up to 30%, depending on the hydraulic diameter, due to reduced viscous resistance.
  • The performance improvement is consistent across both water and liquid metals, though liquid metals exhibit inherently higher heat transfer coefficients.
  • The results confirm that wall slip significantly enhances thermal-hydraulic efficiency in micro-scale heat sinks for high heat dissipation applications.