This paper proposes Quiver, a safe control perturbation framework for smart buildings that uses targeted HVAC actuator adjustments to improve sensor data observability. By applying controlled perturbations, Quiver enables high-accuracy discovery of sensor co-location (98.4%), point type identification (85.3%), and actuator dependency mapping (73.5%) in real-world commercial buildings.
Modern buildings consist of hundreds of sensors and actuators for monitoring and operation of systems such as HVAC, light and security. To enable portable applications in next generation smart buildings, we need models and standardized ontologies that represent these sensors across diverse types of buildings. Recent research has shown that extracting information such as sensor type with available metadata and timeseries data analysis is difficult due to heterogeneity of systems and lack of support for interoperability. We propose perturbations in the control system as a mechanism to increase the observability of building systems to extract contextual information and develop standardized models. We design Quiver, an experimental framework for actuation of building HVAC system that enables us to perturb the control system safely. Using Quiver, we demonstrate three applications using empirical experiments on a real commercial building: colocation of data points, identification of point type and mapping of dependency between actuators. Our results show that we can colocate data points in HVAC terminal units with 98.4 % accuracy and 63 % coverage. We can identify point types of the terminal units with 85.3 % accuracy. Finally, we map the dependency links between actuators with an accuracy of 73.5 %, with 8.1 % and 18.4 % false positives and false negatives respectively.
Motivation & Objective
- Address the challenge of sensor data heterogeneity and lack of standardized ontologies in smart buildings.
- Overcome limitations of metadata and time-series analysis in identifying sensor context, such as point type and location.
- Enable portable, interoperable building applications by extracting contextual information through active control.
- Develop a safe, experimental framework for actuating HVAC systems to probe system behavior without disrupting operations.
- Demonstrate that control perturbations can significantly improve observability of sensor data compared to passive analysis alone.
Proposed method
- Design Quiver, a control framework that safely perturbs HVAC terminal unit (VAV) actuators with constrained input ranges and actuation frequencies.
- Use actuation signals to excite local control systems into unique operating states, making sensor data distinguishable.
- Apply simple data analytics to co-locate sensors based on synchronized responses to perturbations.
- Employ transfer learning with ground-truth point types from one VAV unit to classify types across eight zones.
- Map dependencies between actuators using probabilistic analysis of response correlations across perturbation experiments.
- Implement safety mechanisms including status queries, rollback capabilities, and time-constrained operation (weekends/nights).
Experimental results
Research questions
- RQ1Can control perturbations improve the accuracy of sensor co-location in HVAC systems compared to passive data analysis?
- RQ2To what extent can control perturbations enhance the identification of sensor point types when metadata is unreliable or absent?
- RQ3Can dependency relationships between actuators in a VAV unit be inferred through controlled perturbations and response correlation?
- RQ4How do false positive and false negative rates in dependency mapping vary under real-world operational constraints?
- RQ5Can a safe, single-user control framework enable repeatable and observable system probing for contextual data discovery?
Key findings
- Quiver achieved 98.4% accuracy in co-locating data points within HVAC terminal units, with 63% coverage across the test building.
- Point type identification using transfer learning reached 85.3% accuracy across eight distinct zones in the building.
- Dependency mapping between actuators achieved 73.5% accuracy, with 8.1% false positives and 18.4% false negatives.
- Control perturbations significantly outperformed passive data analysis in identifying sensor relationships, especially in cases where data characteristics were similar during normal operation.
- The framework successfully enabled safe, repeatable experimentation on real HVAC systems, demonstrating feasibility for broader deployment.
- Perturbation-based discovery reduced reliance on manual metadata curation and improved model portability across building systems.