[Paper Review] Reinforcement Learning Testbed for Power-Consumption Optimization
This paper proposes a deep reinforcement learning (DRL)-based controller for data center cooling systems using an open-source EnergyPlus simulation testbed, replacing traditional model-based control. By optimizing a reward function balancing power consumption and temperature stability, the DRL agent achieves 22% lower power usage than the built-in controller while maintaining safe temperature ranges.
Common approaches to control a data-center cooling system rely on approximated system/environment models that are built upon the knowledge of mechanical cooling and electrical and thermal management. These models are difficult to design and often lead to suboptimal or unstable performance. In this paper, we show how deep reinforcement learning techniques can be used to control the cooling system of a simulated data center. In contrast to common control algorithms, those based on reinforcement learning techniques can optimize a system's performance automatically without the need of explicit model knowledge. Instead, only a reward signal needs to be designed. We evaluated the proposed algorithm on the open source simulation platform EnergyPlus. The experimental results indicate that we can achieve 22% improvement compared to a model-based control algorithm built into the EnergyPlus. To encourage the reproduction of our work as well as future research, we have also publicly released an open-source EnergyPlus wrapper interface directly compatible with existing reinforcement learning frameworks.
Motivation & Objective
- To address the inefficiency and complexity of model-based control in data center cooling systems.
- To develop a data-driven, model-free control approach using deep reinforcement learning (DRL) that learns optimal setpoint policies without requiring explicit system models.
- To improve energy efficiency in data centers by minimizing power consumption while maintaining thermal constraints.
- To release a publicly available, Gym-compatible DRL environment for EnergyPlus to enable reproducibility and future research.
Proposed method
- The authors developed an open-source simulation wrapper, EnergyPlusEnv, compatible with the OpenAI Gym interface to interface DRL agents with EnergyPlus simulations.
- The DRL agent uses Trust Region Policy Optimization (TRPO) to learn a control policy that adjusts setpoint temperatures for cooling components like DX coils, CW coils, and fans.
- The environment exposes state variables such as zone temperatures, outdoor weather conditions, and power consumption, and provides a reward signal based on power usage and temperature deviation penalties.
- The reward function is designed to penalize high power consumption and temperatures outside the acceptable range [22.0 °C, 25.0 °C], encouraging energy efficiency and thermal stability.
- The system was trained on multiple weather datasets (CA, CO, FL) and evaluated across diverse climate conditions to assess generalization.
- The DRL agent replaces the built-in setpoint manager and VAV fan controller, enabling end-to-end learning of optimal cooling strategies.
Experimental results
Research questions
- RQ1Can deep reinforcement learning outperform traditional model-based control in reducing data center cooling power consumption?
- RQ2How does the performance of a DRL controller generalize across different weather conditions and climate zones?
- RQ3To what extent can a DRL agent maintain thermal stability while minimizing energy use without relying on system models?
- RQ4Can a publicly released, Gym-compatible simulation environment enable reproducible and extensible research in data center energy optimization?
Key findings
- The DRL-based controller achieved a 22.1% reduction in average power consumption compared to the baseline model-based controller across five test weather datasets.
- The TRPO agent trained on combined CA-CO-FL weather data reduced power usage to 98.3 kW on average, compared to 126.2 kW for the baseline.
- Temperature control was significantly more stable with the DRL agent: standard deviation dropped to 0.28 °C (vs. 0.40 °C for baseline), with 99.6% of readings within the [22.0 °C, 25.0 °C] range.
- The DRL controller maintained consistent performance across diverse climates, including hot (FL) and cold (CO) locations, outperforming the baseline in all test conditions.
- The open-source EnergyPlus wrapper was successfully released on GitHub, enabling integration with existing DRL frameworks and facilitating future research.
- The results demonstrate that DRL can effectively optimize complex, real-world HVAC systems without requiring detailed system models.