[Paper Review] Unified Grid-Forming Control of PMSG Wind Turbines for Fast Frequency Response and MPPT
This paper proposes a unified dual-port grid-forming control for PMSG wind turbines that seamlessly integrates maximum power point tracking (MPPT) and fast frequency response without mode switching. By stabilizing both AC and DC terminals and leveraging rotor speed and pitch control, the controller enables inertial response and primary frequency support while maintaining PLL-free synchronization and improving system frequency stability, with simulations showing improved frequency nadir and RoCoF across wind speeds.
In this work we present a novel dual-port grid-forming control strategy, for permanent magnet synchronous generator wind turbines with back-to-back voltage source converters, that unifies the entire range of functions from maximum power point tracking (MPPT) to providing inertia and fast frequency response without explicit mode switching between grid-following and grid-forming control. The controls impose a well-defined AC voltage at the grid-side converter (GSC) and the machine-side converter (MSC) AC terminals and explicitly stabilize the DC-link capacitor voltage through both GSC and MSC. The wind turbine's kinetic energy storage and curtailment are adjusted through a combination of implicit rotor speed control and pitch angle control and directly determine the operating mode and level of grid support. Moreover, we provide analytical small-signal stability conditions for a simplified system and explicitly characterize the relationship between control gains, curtailment, and the wind turbines steady-state response. Finally, a detailed simulation study is used to validate the results and compared the proposed control with state-of-the-art MPPT control.
Motivation & Objective
- To eliminate the need for explicit mode switching between grid-following and grid-forming control in PMSG wind turbines.
- To enable seamless provision of inertia and fast frequency response using inherent rotor kinetic energy and pitch control.
- To stabilize both AC and DC terminals without relying on a PLL, ensuring robust synchronization.
- To unify MPPT, DC-link voltage control, and grid-support functions within a single control framework.
- To analytically characterize the relationship between control gains, curtailment, and steady-state system response.
Proposed method
- The controller imposes a well-defined AC voltage at both the grid-side converter (GSC) and machine-side converter (MSC) terminals.
- It stabilizes the DC-link capacitor voltage through coordinated control of both GSC and MSC, ensuring stable DC operation.
- The system uses implicit rotor speed control and pitch angle control to manage curtailment and determine grid support capability.
- A dual-port grid-forming control paradigm is applied, ensuring stability if either AC or DC terminal voltage is stable.
- The control strategy dynamically adjusts active power injection based on system frequency deviation, enabling fast frequency response.
- A curtailment strategy is implemented via a predefined delay factor (η_del), allowing controlled operation below MPP for grid support.
Experimental results
Research questions
- RQ1How can a single control strategy unify MPPT and grid-forming functions in PMSG wind turbines without explicit mode switching?
- RQ2What is the relationship between control gains, curtailment, and the steady-state frequency response of the wind turbine?
- RQ3How does the proposed controller enable fast frequency response and inertia support using rotor kinetic energy and pitch control?
- RQ4What are the small-signal stability conditions for the proposed dual-port grid-forming control in a simplified system?
- RQ5How does the controller perform under varying wind speeds and load disturbances compared to conventional MPPT and GFM controls?
Key findings
- The proposed controller improves frequency nadir from 49.397 Hz (GFL MPPT) to 49.644 Hz under low wind speed (8 m/s) conditions.
- At medium wind speed (10 m/s), the frequency nadir improves to 49.613 Hz, and steady-state frequency increases from 49.709 Hz to 49.724 Hz.
- Under high wind speed (12 m/s), the controller maintains a frequency droop coefficient above 2% via K_θ^msc = 1, enabling significant droop response.
- The controller achieves PLL-free synchronization and stable DC voltage control, even during large disturbances.
- The simulation results confirm that the unified control provides superior RoCoF and frequency nadir improvement compared to both GFL MPPT and GFM MPPT strategies.
- The controller’s grid support capability is explicitly linked to the turbine’s operating point, with higher kinetic energy availability at lower wind speeds.
Read this paper