[Paper Review] A Novel Koopman-Inspired Method for the Secondary Control of Microgrids with Grid-Forming and Grid-Following Sources
This paper proposes a data-driven, Koopman-inspired online identification and control method for microgrid secondary voltage and frequency regulation that requires no offline training, ensures BIBO and asymptotic stability, and adapts to nonlinearities and uncertainties from mixed grid-forming and grid-following sources. The method uses adaptive Koopman state estimation via an enhanced OKID algorithm with LQR control, demonstrating robust performance under mode transitions, load/generation changes, and measurement noise in 4-bus and 13-bus test systems.
This paper proposes an online data-driven Koopman-inspired identification and control method for microgrid secondary voltage and frequency control. Unlike typical data-driven methods, the proposed method requires no warm-up training yet with guaranteed bounded-input-bounded-output (BIBO) stability and even asymptotic stability under some mild conditions. The proposed method estimates the Koopman state space model adaptively so as to perform effective secondary voltage and frequency control that can handle microgrid nonlinearity and uncertainty. Case studies in the 4-bus and 13-bus microgrid test systems (with grid-forming and grid-following sources) demonstrate the effectiveness and robustness of the proposed identification and control method subject to the change of operating conditions and large disturbances (e.g., microgrid mode transitions, generation/load variations) even with measurement noises and time delays.
Motivation & Objective
- Address the challenge of secondary voltage and frequency control in microgrids with mixed grid-forming and grid-following converters under large disturbances and uncertainty.
- Overcome limitations of model-based methods requiring accurate physical models and model-free methods like PI control that lack adaptiveness and robustness.
- Develop a data-driven control approach that requires no warm-up training and guarantees bounded-input-bounded-output (BIBO) and asymptotic stability.
- Enable real-time, adaptive control using only a small window of synchrophasor (e.g., microPMU) measurements from DER terminals.
- Ensure effective control performance under dynamic conditions such as islanding transitions, load variations, and time delays, even with measurement noise.
Proposed method
- Leverages Koopman operator theory to embed nonlinear microgrid dynamics into a linear state-space representation via Koopman observables.
- Proposes an enhanced Observer Kalman Filter Identification (OKID) algorithm to estimate the Koopman state space model online using phasor angle and voltage measurements.
- Introduces an adaptive regularization parameter $\gamma_{\text{opt}}$ that is updated every 0.6 seconds to improve identification accuracy and stability.
- Employs Linear Quadratic Regulator (LQR) control based on the online-estimated Koopman model for secondary voltage and frequency control.
- Uses a small data window (e.g., 10–20 samples) of synchrophasor data from DERs to enable real-time implementation.
- Ensures stability through theoretical guarantees: BIBO stability is proven, and asymptotic stability is achieved under mild conditions on the system and observer design.
Experimental results
Research questions
- RQ1Can a data-driven Koopman-inspired method achieve stable and accurate secondary voltage and frequency control in microgrids without requiring offline training or prior knowledge of system models?
- RQ2How does the proposed adaptive Koopman identification method perform under large disturbances such as islanding transitions and load/generation variations?
- RQ3What is the impact of using an adaptive regularization parameter $\gamma_{\text{opt}}$ on the accuracy and robustness of Koopman model identification in nonlinear microgrid systems?
- RQ4How does the proposed method compare to conventional OKID, EDMDc, and PI control in terms of transient response and steady-state performance?
- RQ5Is the proposed method computationally feasible for real-time implementation in distribution-level microgrids?
Key findings
- The proposed Koopman-inspired enhanced OKID with LQR control restored voltage and frequency to nominal values within 0.5 seconds after islanding detection in the 13-bus test system.
- The method achieved a runtime of approximately 20ms per control step when $\gamma_{\text{opt}}$ was not updated, and under 500ms when updated, both within the 30ms control time step and below the 0.6s update interval.
- Compared to PI control, the proposed method eliminated steady-state errors and avoided large overshoots, even with suboptimal tuning.
- The method outperformed conventional OKID with LQR and classical EDMDc (least-squares Koopman) in suppressing voltage and frequency oscillations after disturbances.
- The adaptive $\gamma_{\text{opt}}$ significantly improved identification accuracy and control performance under nonlinear dynamics and measurement noise.
- The method demonstrated robustness to time delays, measurement noise, and large disturbances such as solar irradiance drops and load changes in both 4-bus and 13-bus systems.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.
Read this paper on NubintThis review was generated by AI from the original paper. Please check the paper before citing it.