[Paper Review] CD-HOC: Indoor Human Occupancy Counting using Carbon Dioxide Sensor Data
CD-HOC proposes a novel method for indoor human occupancy counting using carbon dioxide (CO₂) sensor data, leveraging seasonal-trend decomposition (Loess and moving average) to model CO₂ components, applying regression models to each component, and using a zero-pattern adjustment to enhance accuracy. The approach improves occupancy estimation accuracy by 4.33% in a small room (94.68%) and 8.46% in a cinema theatre compared to support vector regression baseline.
Human occupancy information is crucial for any modern Building Management System (BMS). Implementing pervasive sensing and leveraging Carbon Dioxide data from BMS sensor, we present Carbon Dioxide - Human Occupancy Counter (CD-HOC), a novel way to estimate the number of people within a closed space from a single carbon dioxide sensor. CD-HOC de-noises and pre-processes the carbon dioxide data. We utilise both seasonal-trend decomposition based on Loess and seasonal-trend decomposition with moving average to factorise carbon dioxide data. For each trend, seasonal and irregular component, we model different regression algorithms to predict each respective human occupancy component value. We propose a zero pattern adjustment model to increase the accuracy and finally, we use additive decomposition to reconstruct the prediction value. We run our model in two different locations that have different contexts. The first location is an academic staff room and the second is a cinema theatre. Our results show an average of 4.33% increment in accuracy for the small room with 94.68% indoor human occupancy counting and 8.46% increase for the cinema theatre in comparison to the accuracy of the baseline method, support vector regression.
Motivation & Objective
- To develop a low-cost, scalable method for indoor human occupancy counting using existing CO₂ sensors in Building Management Systems (BMS).
- To address the challenge of accurate occupancy estimation in closed indoor environments without relying on cameras or RFID.
- To improve upon baseline methods like support vector regression by incorporating temporal decomposition and adaptive adjustment of zero-occupancy patterns.
- To validate the method in diverse indoor settings with varying occupancy dynamics, such as a staff room and cinema theatre.
Proposed method
- The method applies seasonal-trend decomposition using Loess (STL) and moving average to decompose CO₂ time series into trend, seasonal, and irregular components.
- Each decomposed component (trend, seasonal, irregular) is modeled independently using regression algorithms to predict its contribution to occupancy.
- A zero-pattern adjustment model is introduced to correct for underestimation during periods of low or zero occupancy, improving model robustness.
- The final occupancy prediction is reconstructed using additive decomposition, combining the predicted components into a unified estimate.
- The model is trained and evaluated on real CO₂ sensor data collected from two distinct indoor environments: a small academic staff room and a cinema theatre.
Experimental results
Research questions
- RQ1Can CO₂ sensor data alone be effectively leveraged to estimate indoor human occupancy with high accuracy?
- RQ2How do seasonal and trend decomposition techniques improve the modeling of CO₂-based occupancy estimation?
- RQ3To what extent does a zero-pattern adjustment model enhance prediction accuracy in low-occupancy scenarios?
- RQ4How does the proposed method compare to baseline regression models like support vector regression in diverse indoor environments?
Key findings
- The CD-HOC model achieved a 94.68% accuracy in estimating human occupancy in a small academic staff room, representing a 4.33% improvement over the support vector regression baseline.
- In a cinema theatre setting, the model improved accuracy by 8.46% compared to the baseline, demonstrating strong performance in high-variability occupancy environments.
- The use of both Loess-based STL and moving average decomposition enabled effective separation of CO₂ signal components, enhancing model interpretability and performance.
- The zero-pattern adjustment model significantly reduced underestimation errors during periods of low or no occupancy, contributing to overall accuracy gains.
Read this paper