[Paper Review] Comparative assessment of typical controlrealizations of grid forming converters based ontheir voltage source behaviour
This paper compares three grid-forming converter (GFC) control structures—cascaded voltage/current control, inner current control only, and no inner loop—focusing on their ability to emulate a voltage source behind an impedance. It finds that inner loops, especially cascaded control, can cause instability under weak grids and limit stable operation to narrow impedance ranges, while GFCs without inner loops better maintain harmonic and unbalance current handling and stability across network strengths.
The converter control functions to provide the capabilities similar to synchronous generators are referred to as grid forming converters (GFC). Identical to a synchronous machine, a grid forming converter is expected to behave as a voltage source behind an impedance beyond the control bandwidth. However, GFC's realization has been different, with some utilizes inner current and voltage controllers while others do not. This paper studies the impact of the inner loop on the grid forming converter's ability to behave as a voltage source behind an impedance. Three of the most popular GFC structures, 1) GFC with cascaded voltage and current control, 2) with inner current control, 3) with no inner loop, are chosen for the comparison. The analysis revealed that MW level GFC with inner loops could potentially go unstable under weak power system. Additionally, the GFC with cascaded control can only operate stably within a narrow range of network impedances. Furthermore, it is also shown that slow response behavior based on cascaded inner loop can impact on dynamic reactive and active power-sharing.
Motivation & Objective
- To evaluate how different inner control loop designs affect the voltage source behavior of grid-forming converters (GFCs).
- To assess the stability and dynamic performance of GFCs with varying control architectures under weak and strong power systems.
- To investigate the impact of inner loops on electromechanical oscillation damping and fault response characteristics.
- To examine the ability of GFCs to act as natural sinks for harmonics and unbalanced currents.
- To identify control design trade-offs affecting system strength, stability margins, and compatibility with RMS and EMT simulation models.
Proposed method
- Conducts small-signal stability analysis using impedance-based modeling to compare three GFC control structures: cascaded voltage/current control, inner current control only, and no inner loop.
- Derives equivalent Thevenin impedance models for each GFC configuration to assess voltage source behavior across 5 Hz – 1 kHz.
- Performs eigenvalue analysis to evaluate electromechanical mode damping and stability margins under varying network strengths.
- Uses EMT simulation to validate dynamic performance and current limiting behavior during faults and load changes.
- Analyzes harmonic and unbalance current handling capabilities, particularly for GFCs with and without inner loops.
- Compares the impact of switching frequency and control design on stability and system strength sensitivity.
Experimental results
Research questions
- RQ1How does the presence of an inner current loop affect the voltage source behavior of grid-forming converters in weak networks?
- RQ2What are the stability limits of GFCs with cascaded voltage and current control under varying network impedances?
- RQ3How does the choice of control structure influence the damping of electromechanical oscillations in GFCs?
- RQ4Can GFCs without inner loops naturally handle harmonics and unbalanced currents without additional control loops?
- RQ5What are the implications of inner loop dynamics on current limiting and fault ride-through performance?
Key findings
- GFCs with cascaded voltage and current control exhibit instability under weak grid conditions due to high-frequency oscillations and poor damping of electromechanical modes.
- The stable operating range for cascaded-control GFCs is narrow, with both upper and lower bounds on network impedance; instability occurs at low and high network strengths.
- GFCs without inner loops maintain stable voltage source behavior across a wide range of network impedances and show superior damping of electromechanical modes.
- Only GFCs without inner loops naturally act as sinks for harmonics and unbalanced currents within hardware limits, while those with inner loops require additional control loops.
- The response speed of cascaded inner loops degrades dynamic reactive and active power sharing, especially during disturbances.
- GFCs with higher switching frequencies and optimized control design can achieve similar damping performance as no-inner-loop GFCs, even with cascaded control.
Read this paper