[Paper Review] Decentralized Robust Control for Damping Inter-area Oscillations in Power Systems

Jianming Lian, Shaobu Wang|arXiv (Cornell University)|Jan 8, 2017
Power System Optimization and StabilityEngineering26 references8 citations
TL;DR

This paper proposes a decentralized robust control strategy that enhances inter-area oscillation damping by directly modulating real power via turbine governing systems, using only local signals. The method achieves robust performance across varying operating conditions and system topologies, improving damping ratios by up to 8.5% in tested systems, enabling higher power transfer and enhanced transmission utilization without relying on wide-area signals or complex coordination.

ABSTRACT

As power systems become more and more interconnected, the inter-area oscillations has become a serious factor limiting large power transfer among different areas. Underdamped (Undamped) inter-area oscillations may cause system breakup and even lead to large-scale blackout. Traditional damping controllers include Power System Stabilizer (PSS) and Flexible AC Transmission System (FACTS) controller, which adds additional damping to the inter-area oscillation modes by affecting the real power in an indirect manner. However, the effectiveness of these controllers is restricted to the neighborhood of a prescribed set of operating conditions. In this paper, decentralized robust controllers are developed to improve the damping ratios of the inter-area oscillation modes by directly affecting the real power through the turbine governing system. The proposed control strategy requires only local signals and is robust to the variations in operation condition and system topology. The effectiveness of the proposed robust controllers is illustrated by detailed case studies on two different test systems.

Motivation & Objective

  • To address the limitations of conventional PSS and FACTS controllers in damping inter-area oscillations under varying operating conditions and system topology.
  • To develop a decentralized control strategy that improves damping ratios without relying on wide-area measurements or centralized coordination.
  • To ensure robustness to system stress levels, N-1 contingencies, and parameter variations through local feedback only.
  • To enable higher power transfer capacity by enhancing small signal stability in interconnected power systems.

Proposed method

  • The proposed controller introduces an auxiliary control signal into the turbine governing system to generate an additional mechanical torque on the generator rotor, directly affecting real power output.
  • The control design is based on robust control theory, specifically H∞ or μ-synthesis techniques, to ensure stability across a range of operating points and system configurations.
  • Only local signals—such as rotor speed and mechanical power—are used, eliminating dependency on wide-area measurement systems (WAMS) or global signals.
  • The controller is implemented independently at each generator with steam valve governors, enabling decentralized operation without coordination with other controllers.
  • The method is validated through eigenvalue analysis and small-signal stability assessment under various stress levels and N-1 contingency scenarios.
  • The approach is extended to modified systems with added generators to test robustness under topology changes and ensure consistent damping improvement.

Experimental results

Research questions

  • RQ1Can a decentralized control strategy based on local signals effectively improve damping of inter-area oscillations without relying on wide-area measurements?
  • RQ2How does the proposed controller perform under varying system stress levels and operating conditions?
  • RQ3What is the impact of system topology changes, such as line tripping, on the controller’s effectiveness and damping ratio?
  • RQ4Can the controller maintain robust performance when applied to different generator types, such as those with steam valve governors?
  • RQ5How does the controller compare to conventional PSS and FACTS-based controllers in terms of robustness and stability margins?

Key findings

  • The proposed decentralized robust controller improved the damping ratio of the 0.40 Hz inter-area mode from 0.86% (with PSS only) to 7.72% in the 17-machine system after adding a controller at generator G18.
  • In the modified 17-machine system with an additional robust controller at G18, the damping ratio of the 0.40 Hz mode reached 8.21% under base case conditions, demonstrating robustness to system stress.
  • After 51 N-1 contingency cases involving line tripping, the damping ratio of the 0.40 Hz mode remained above 6.56% with the proposed controller, confirming robustness to topology changes.
  • The controller maintained effective damping across all tested system stress levels, with no degradation in performance under varying loading or network configurations.
  • The method achieved consistent damping improvements even when the original system lacked controllers in critical areas, highlighting the importance of strategic placement in poorly damped inter-area ties.
  • The results confirm that direct real power modulation via turbine governors provides a cost-effective, scalable, and robust alternative to PSS and FACTS-based damping solutions.