[Paper Review] Grid-Forming Converters control based on DC voltage feedback
This paper proposes a grid-forming converter (GFC) control strategy that incorporates DC voltage feedback to prevent DC voltage collapse during large load disturbances, enhancing system stability. By integrating DC voltage feedback into existing control methods like Frequency Droop Control, Virtual Synchronous Machine (VSG), and dispatchable Virtual Oscillator Control (dVOC), the method ensures coordinated DC and AC side stability, verified via IEEE-9 bus system simulations with improved robustness under large disturbances.
The renewable energy is connected to the power grid through power electronic converters, which are lack of make the inertia of synchronous generator/machine (SM) be lost. The increasing penetration of renewable energy in power system weakens the frequency and voltage stability. The Grid-Forming Converters (GFCs) simulate the function of synchronous motor through control method in order to improve the stability of power grid by providing inertia and stability regulation mechanism. This kind of converter control methods include virtual synchronous machine, schedulable virtual oscillator control and so on. These control method mainly use AC side state feedback and do not monitor the DC side state. This paper analyzes the control strategy of GFC considering power grid stability, including Frequency Droop Control, Virtual Synchronous Machine Control and dispatchable Virtual Oscillator Control. The DC side voltage collapse problem is found when a large load disturbance occurs. The control methods of GFC considering DC side voltage feedback are proposed, which can ensure the synchronization characteristics of grid connection and solve the problem of DC side voltage collapse. The proposed method is verified by IEEE-9 bus system, which shows the effectiveness of the proposed method.
Motivation & Objective
- To address the instability of grid-forming converters (GFCs) under large load disturbances due to unmonitored DC-side dynamics.
- To identify the risk of DC voltage collapse in existing GFC control strategies that rely solely on AC-side state feedback.
- To develop a unified control framework integrating DC voltage feedback into established GFC methods (e.g., Frequency Droop, VSG, dVOC) for improved system robustness.
- To ensure coordinated stability of both DC and AC sides during large disturbances, maintaining synchronization and power quality.
Proposed method
- Introduces DC voltage feedback into the control loop of existing GFC strategies, modifying the original control laws to include DC voltage as a feedback variable.
- Adapts three standard GFC control methods—Frequency Droop Control, Virtual Synchronous Machine (VSG), and dVOC—by adding DC voltage feedback to stabilize the DC link.
- Derives modified control equations (7, 9, 11) that adjust the active power reference based on DC voltage deviation, preventing overcurrent and voltage collapse.
- Uses a unified GFC model including DC-link capacitance, inverter, filter, and grid connection dynamics to analyze system behavior under disturbance.
- Implements a saturation-based current limiting mechanism (Eq. 12) to prevent DC current over-limiting, now augmented with DC voltage feedback for improved response.
- Validates the proposed method using a detailed IEEE-9 bus system model in MATLAB/Simulink under large load step disturbances (0 to 0.9 p.u.).
Experimental results
Research questions
- RQ1Can DC voltage feedback prevent DC voltage collapse in GFCs during large load disturbances when traditional AC-side-only feedback is used?
- RQ2How does integrating DC voltage feedback improve the stability of Frequency Droop Control, VSG, and dVOC under large disturbances?
- RQ3To what extent does DC voltage feedback coordination enhance the robustness of both DC and AC side dynamics in grid-forming converters?
- RQ4Does the proposed feedback strategy maintain synchronization and power quality during transient events without compromising AC-side performance?
- RQ5Can the proposed method stabilize the system within a short transient time (e.g., ~1.5 seconds) after a large disturbance?
Key findings
- The proposed DC voltage feedback method successfully prevents DC voltage collapse during large load disturbances (0 to 0.9 p.u.) in all tested GFC control strategies—Frequency Droop Control, VSG, and dVOC.
- DC side current remains within safe limits and stabilizes rapidly, with no overcurrent or voltage collapse observed in simulations.
- All system states—frequency, active power, and output voltage amplitude—stabilize within approximately 1.5 seconds after a large disturbance, ensuring system resilience.
- The method maintains stable synchronization across all buses in the IEEE-9 bus system, with synchronized electrical quantities across nodes post-disturb.
- The integration of DC voltage feedback significantly improves system robustness without degrading AC-side performance, as confirmed by consistent transient response across all control methods.
- The simulation results demonstrate that DC voltage feedback enables coordinated control of DC and AC sides, making the system more resilient to large disturbances than conventional GFC control strategies.