TL;DR

This paper investigates interactions between grid-forming converters (GFCs) and synchronous machines (SMs) in low-inertia power systems using a high-fidelity electromagnetic transients (EMT) simulation of the IEEE 9-bus system. It evaluates four GFC control strategies—droop, virtual synchronous machine (VSM), matching control, and dispatchable virtual oscillator control (dVOC)—under large disturbances and current limitations, finding that GFCs improve frequency stability but that dc/ac current limits can destabilize VSM, droop, and dVOC due to fast converter–slow SM dynamics, while matching control remains robust.

ABSTRACT

An inevitable consequence of the global power system transition towards nearly 100% renewable-based generation is the loss of conventional bulk generation by synchronous machines, their inertia, and accompanying frequency and voltage control mechanisms. This gradual transformation of the power system to a low-inertia system leads to critical challenges in maintaining system stability. Novel control techniques for converters, so-called grid-forming strategies, are expected to address these challenges and replicate functionalities that so far have been provided by synchronous machines. We present a low-inertia high-fidelity case study that includes synchronous machines and models of grid-forming converters. We study interactions between synchronous machines and converters and analyze the response of various grid-forming control approaches to contingencies, i.e., large changes in load and the loss of a synchronous machine. Our case study highlights the positive impact of the grid-forming converters on frequency stability and analyze the potential limitations of each control technique when interacting with synchronous machines. Our studies also analyze how and when the interaction between the fast grid-forming converter, the dc source and ac current limitations, and the slow synchronous machine dynamics contributes to system instability. Lastly, we introduce an effective solution to address the instability issues due to the GFCs ac and dc current limitation.

Motivation & Objective

  • To analyze the dynamic interactions between grid-forming converters (GFCs) and synchronous machines (SMs) in low-inertia power systems during large disturbances.
  • To evaluate the performance of four GFC control strategies—droop, VSM, matching control, and dVOC—on key frequency stability metrics such as RoCoF and frequency nadir.
  • To investigate how dc and ac current limitations interact with fast GFC dynamics and slow SM dynamics to induce instability.
  • To identify control strategies that maintain stability under mixed GFC–SM operation and current constraints.
  • To propose a solution to mitigate instability caused by current limitations in GFCs

Proposed method

  • Conducted a high-fidelity electromagnetic transients (EMT) simulation of the IEEE 9-bus test system with detailed models of SMs and GFCs.
  • Implemented four GFC control strategies: droop control, virtual synchronous machine (VSM), matching control, and dispatchable virtual oscillator control (dVOC), each with cascaded inner-loop control for ac voltage and current.
  • Integrated dynamic models of the dc-link capacitor, dc power source response time, and current limits into the GFC control framework.
  • Tuned control parameters to ensure identical steady-state load-sharing across all GFC types and SMs using matching droop gain criteria derived from equations (29)–(32).
  • Performed contingency studies including large load changes and loss of a synchronous machine to assess transient response and stability.
  • Used online models from the authors’ repository [23] to ensure reproducibility and transparency of the simulation setup.

Experimental results

Research questions

  • RQ1How do different grid-forming control strategies (droop, VSM, matching control, dVOC) perform in terms of frequency stability metrics like RoCoF and frequency nadir under large load disturbances?
  • RQ2What is the impact of dc and ac current limitations on the stability of GFC–SM systems, particularly when fast GFC dynamics interact with slow SM dynamics?
  • RQ3Which GFC control strategy is most resilient to instability caused by current limiting and dynamic interactions with SMs?
  • RQ4How does the interaction between fast GFC synchronization and slow SM frequency dynamics contribute to system instability?
  • RQ5Can a fully converter-based (all-GFC) system exhibit greater resilience than a mixed SM–GFC system under contingency conditions?

Key findings

  • Grid-forming converters significantly improve frequency stability metrics such as RoCoF and frequency nadir compared to conventional grid-following control.
  • Limiting the dc or ac current of GFCs can destabilize VSM, droop control, and dVOC due to the interaction between fast converter dynamics and slow SM dynamics.
  • Matching control is the only GFC strategy that remains stable under current limitations and dynamic interactions with SMs, demonstrating robustness.
  • A potentially destabilizing interaction arises between the fast synchronization of GFCs and the slow frequency response of SMs, especially under large disturbances.
  • An all-GFC system (no-inertia) can exhibit greater resilience than a mixed SM–GFC system under contingency conditions, challenging the assumption that SM inertia is always beneficial.
  • The study identifies a critical instability mechanism caused by current limits and dynamic misalignment between fast GFCs and slow SMs, which is mitigated by the proposed solution involving coordinated control design.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.