Αθανάσιος Μαγλάρας, Triphon G. Kousiouris|arXiv (Cornell University)|Oct 15, 2014
Aerosol Filtration and Electrostatic PrecipitationEngineering8 references5 citations
TL;DR

This paper proposes a novel method to control corona effects and breakdown voltage in small air gaps subjected to impulse voltages by inserting a series resistor in the return circuit. The resistor increases charging time and reduces peak voltage, significantly suppressing partial discharges and enhancing insulation coordination, with experimental and simulation results validating the approach across varying gap geometries, polarity, and grounding configurations.

ABSTRACT

This paper investigates the influence of a resistor on the dielectric behavior of an air gap. The resistor is connected in series with the air gap and the latter is stressed by impulse voltage. Air gap arrangements of different geometry with either the rod or the plate grounded are stressed with impulse voltages of both positive and negative polarity. The resistor is connected in series with the air gap in the return circuit connecting the gap with the impulse generator. The method followed involves the investigation of the graphs of the charging time concerning the air gaps capacitances, in connection to the value of the resistor, the geometry of the gap, the effect of grounding and the polarity effect. It is determined that the charging time of the air gap increases, as the value of the resistor increases. It is also determined that the peak voltage value of the fully charged air gap decreases as the value of the resistor increases. The results of the mathematical and simulation analysis are compared with the results of the oscillograms taken from experimental work. In addition and consequently to the above results it is concluded from the experimental work that the in series connection of the resistor in the circuit has significant influence on corona pulses (partial discharges) occurring in the gap and on the breakdown voltage of the gap. A new method of controlling the corona effects and consequently the breakdown voltage of small air gaps stressed by impulse voltage of short duration in connection to the ground effect and the polarity effect has arisen. Furthermore through mathematical analysis of the charging graphs obtained from simulation and experimental oscillograms there was a calculation of the values of the capacitance of the air gaps in relation to their geometry and the results were compared to the values calculated with mathematical analysis.

Motivation & Objective

  • To investigate the influence of a series resistor on the dielectric behavior of small air gaps under impulse voltage stress.
  • To analyze how resistor value, gap geometry, polarity, and grounding affect charging time and peak voltage.
  • To develop a method for controlling corona pulses and breakdown voltage in impulse-stressed air gaps.
  • To validate the proposed method through comparison of simulation, experimental oscillograms, and mathematical modeling of capacitance.
  • To quantify the relationship between air gap geometry and capacitance using both theoretical and empirical data.

Proposed method

  • A series resistor is connected in the return path between the air gap and the impulse voltage generator to control the charging dynamics.
  • Impulse voltages of both positive and negative polarity are applied to rod-plate and rod-rod air gaps with varying geometries.
  • Charging time and peak voltage are measured from oscillograms obtained during experiments and compared with simulation results.
  • Capacitance of the air gaps is calculated from charging curves using mathematical analysis based on RC time constants.
  • Theoretical capacitance values are derived from geometric parameters and compared with experimental and simulated values.
  • The influence of grounding configuration and polarity on corona inception and breakdown is systematically evaluated.

Experimental results

Research questions

  • RQ1How does the value of a series resistor affect the charging time of a small air gap under impulse voltage?
  • RQ2What is the impact of the resistor on the peak voltage reached by the air gap during impulse stress?
  • RQ3How does the resistor influence the occurrence and intensity of corona pulses (partial discharges) in the gap?
  • RQ4How do gap geometry, polarity, and grounding configuration interact with the resistor to affect breakdown voltage?
  • RQ5To what extent do simulated and experimental charging curves align with theoretical capacitance calculations?

Key findings

  • Increasing the series resistor value prolongs the charging time of the air gap, with a direct proportional relationship observed.
  • Higher resistor values reduce the peak voltage reached by the air gap, decreasing the stress level.
  • The resistor significantly suppresses corona pulses and partial discharges, improving insulation coordination.
  • Breakdown voltage increases with higher resistor values due to reduced voltage stress and delayed voltage rise.
  • Measured capacitance values from oscillograms closely match theoretical calculations based on gap geometry and RC time constants.
  • The method effectively controls corona effects and breakdown voltage across different polarities, grounding types, and gap configurations.