[Paper Review] Simultaneous identification of linear building dynamic model and disturbance using sparsity-promoting optimization
This paper proposes SPDIR, a convex optimization method that simultaneously identifies a linear time-invariant (LTI) thermal model of a building and a transformed, sparsity-promoting representation of unmeasured disturbances—such as occupant-induced heat gains—using ℓ₁-regularization. The method guarantees stability and positive DC gains, enabling fully automated, self-learning control without human intervention, with demonstrated accuracy on both simulated and real building data.
We propose a method that simultaneously identifies a linear time-invariant model of a building's temperature dynamics and a transformed version of the unmeasured disturbance affecting the building. Our method uses l1-regularization to encourage the identified disturbance to be approximately sparse, which is motivated by the slowly-varying nature of occupancy that determines the disturbance. The proposed method involves solving a convex optimization problem that guarantees the identified black-box model possesses known properties of the plant, especially input-output stability and positive DC gains. These features enable one to use the method as part of a self-learning control system in which the model of the building is updated periodically without requiring human intervention. Results from the application of the method on data from a simulated and real building are provided.
Motivation & Objective
- To address the challenge of identifying accurate building thermal models in the presence of unmeasured, slowly-varying disturbances such as occupant-induced heat gains.
- To develop a system identification method that guarantees key physical properties—specifically input-output stability and positive DC gains—without requiring expert validation.
- To enable fully automated, periodic model updates for self-learning control systems by avoiding non-convex optimization and human intervention.
- To improve robustness and accuracy in model identification by exploiting the sparsity of transformed disturbances due to the piecewise-constant nature of occupancy patterns.
- To provide a practical, scalable solution for real-time building control that does not rely on specially collected data or prior knowledge of disturbance profiles.
Proposed method
- Formulates a convex optimization problem that jointly estimates the LTI plant model and a transformed version of the unmeasured disturbance using ℓ₁-regularization to promote sparsity in the disturbance estimate.
- Imposes linear inequality constraints on the optimization to enforce known physical properties: input-output stability and positive DC gains for relevant input-output pairs.
- Uses a transformed disturbance representation that approximates slowly-varying or piecewise-constant occupancy loads as sparse signals in the time domain.
- Employs a critical regularization parameter λ_max derived for ℓ₁-regularized problems with linear constraints, providing a principled starting point for tuning λ.
- Solves a constrained least-squares problem with ℓ₁-regularization, ensuring the solution is globally optimal and computationally efficient.
- Applies the method to both simulated and real building data, using input-output temperature and control signal measurements to identify the model and disturbance.
Experimental results
Research questions
- RQ1Can a convex optimization framework simultaneously identify a stable, physically plausible LTI building thermal model and a sparse representation of unmeasured disturbances?
- RQ2How does ℓ₁-regularization improve disturbance estimation when the true disturbance is slowly varying or piecewise-constant?
- RQ3To what extent can the method guarantee stability and positive DC gains in the identified model without requiring human validation?
- RQ4How does the performance of the proposed SPDIR method compare to existing non-convex methods (e.g., LD method) in terms of accuracy and robustness under poor initialization?
- RQ5Can the method be effectively applied to real building data where ground truth disturbance is unavailable?
Key findings
- The SPDIR method achieves an RMS prediction error of 1.2 °C for zone temperature in simulation scenarios, outperforming the LD method when initial guesses are poor.
- On real building data, the SPDIR method achieves an RMS prediction error of 0.3 °C, demonstrating strong fit to actual temperature dynamics.
- The estimated transformed disturbance captures the trend of true disturbances even when they are not piecewise-constant, with low magnitudes during unoccupied nighttime periods.
- The method guarantees stability and positive DC gains, which are not ensured by prior methods such as the LD method that rely on non-convex optimization.
- The SPDIR method outperforms the Box-Jenkins ARMAX method in both simulation and real data experiments, particularly in handling colored disturbances.
- The determination of λ_max for constrained ℓ₁-regularized problems provides a reliable starting point for regularization tuning, enhancing robustness and convergence.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.
Read this paper on NubintThis review was generated by AI from the original paper. Please check the paper before citing it.