TL;DR

This paper critically examines the branch flow convexification method and ADMM-based approaches for solving the non-convex AC optimal power flow (OPF) problem in radial distribution networks. It demonstrates that the Farivar-Low convexification is not exact due to physical model misinterpretations and unrealistic assumptions, and shows ADMM fails to converge in cases with shunt capacitors or OLTCs, leading to a proposed exact, non-convex OPF algorithm for radial systems.

ABSTRACT

The optimal power-flow problem (OPF) has played a key role in the planning and operation of power systems. Due to the non-linear nature of the AC power-flow equations, the OPF problem is known to be non-convex, therefore hard to solve. Most proposed methods for solving the OPF rely on approximations that render the problem convex, but that may yield inexact solutions. Recently, Farivar and Low proposed a method that is claimed to be exact for radial distribution systems, despite no apparent approximations. In our work, we show that it is, in fact, not exact. On one hand, there is a misinterpretation of the physical network model related to the ampacity constraint of the lines' current flows. On the other hand, the proof of the exactness of the proposed relaxation requires unrealistic assumptions related to the unboundedness of specific control variables. We also show that the extension of this approach to account for exact line models might provide physically infeasible solutions. Recently, several contributions have proposed OPF algorithms that rely on the use of the alternating-direction method of multipliers (ADMM). However, as we show in this work, there are cases for which the ADMM-based solution of the non-relaxed OPF problem fails to converge. To overcome the aforementioned limitations, we propose an algorithm for the solution of a non-approximated, non-convex OPF problem in radial distribution systems that is based on the method of multipliers, and on a primal decomposition of the OPF. This work is divided in two parts. In Part I, we specifically discuss the limitations of BFM and ADMM to solve the OPF problem. In Part II, we provide a centralized version and a distributed asynchronous version of the proposed OPF algorithm and we evaluate its performances using both small-scale electrical networks, as well as a modified IEEE 13-node test feeder.

Motivation & Objective

  • To investigate the theoretical and practical limitations of the Farivar-Low branch flow convexification method for radial distribution network OPF.
  • To assess the convergence behavior of ADMM-based decomposition for non-relaxed, non-convex AC OPF in radial networks.
  • To identify physical and modeling assumptions that invalidate the claimed exactness of the Farivar-Low relaxation.
  • To demonstrate cases where ADMM fails to converge due to non-convex line constraints from shunt components or OLTCs.
  • To lay the foundation for a non-approximated, non-convex OPF algorithm that ensures global optimality and convergence in radial distribution systems.

Proposed method

  • Analyzes the Farivar-Low convexification by identifying misinterpretations in the line current ampacity constraint and the physical network model.
  • Reveals that the proof of exactness relies on unrealistic assumptions: full controllability of all loads/generators and no upper bounds on controllable loads.
  • Applies ADMM decomposition to the non-relaxed AC OPF problem, using dual decomposition and alternating updates of primal and dual variables.
  • Derives the ADMM subproblems for each network line, showing that the line problem becomes non-convex when shunt admittances or OLTC ratios are variables.
  • Uses numerical case studies with varying shunt capacitor sizes and OLTCs to demonstrate ADMM convergence failure through residual and voltage evolution plots.
  • Proposes a new algorithm for solving the non-convex, non-relaxed OPF problem in radial networks, to be detailed in Part II of the work.

Experimental results

Research questions

  • RQ1Is the Farivar-Low branch flow convexification method truly exact for radial distribution networks under realistic physical constraints?
  • RQ2What assumptions underlie the claimed exactness of the Farivar-Low relaxation, and how do they violate practical system operation?
  • RQ3Under what conditions does the ADMM-based solution of the non-relaxed AC OPF fail to converge in radial distribution networks?
  • RQ4How do shunt components (e.g., switched capacitors) and OLTCs affect the convexity of the ADMM subproblems in the OPF formulation?
  • RQ5Can a non-approximated, non-convex OPF algorithm be designed to ensure global optimality and convergence in radial distribution systems?

Key findings

  • The Farivar-Low convexification is not exact due to a misinterpretation of the line current ampacity constraint in the physical network model.
  • The proof of exactness relies on unrealistic assumptions: full controllability of all loads/generators and no upper bounds on controllable power injections.
  • ADMM fails to converge in cases with shunt capacitors when the shunt susceptance exceeds the line's negative susceptance, making the line subproblem non-convex.
  • Inclusion of OLTCs as control variables introduces non-convexity into the line subproblems due to quadratic dependence on the tap ratio, causing ADMM convergence failure.
  • Numerical results show oscillatory behavior in primal and dual residuals, and voltage magnitudes, when ADMM fails to converge in Case II.
  • The paper establishes that both the Farivar-Low relaxation and ADMM-based methods have fundamental limitations in practical radial distribution network OPF applications.