Skip to main content
QUICK REVIEW

[Paper Review] Two-Timescale Voltage Control in Distribution Grids Using Deep Reinforcement Learning

Qiuling Yang, Gang Wang|arXiv (Cornell University)|Apr 19, 2019
Optimal Power Flow DistributionEngineering27 references37 citations
TL;DR

This paper presents a two-timescale scheme that jointly controls capacitors (slow timescale via deep RL) and smart inverters (fast timescale via convex optimization) to regulate voltages in distribution grids, validated on a 47-bus network and the IEEE 123-bus feeder.

ABSTRACT

Modern distribution grids are currently being challenged by frequent and sizable voltage fluctuations, due mainly to the increasing deployment of electric vehicles and renewable generators. Existing approaches to maintaining bus voltage magnitudes within the desired region can cope with either traditional utility-owned devices (e.g., shunt capacitors), or contemporary smart inverters that come with distributed generation units (e.g., photovoltaic plants). The discrete on-off commitment of capacitor units is often configured on an hourly or daily basis, yet smart inverters can be controlled within milliseconds, thus challenging joint control of these two types of assets. In this context, a novel two-timescale voltage regulation scheme is developed for distribution grids by judiciously coupling data-driven with physicsbased optimization. On a faster timescale, say every second, the optimal setpoints of smart inverters are obtained by minimizing instantaneous bus voltage deviations from their nominal values, based on either the exact alternating current power flow model or a linear approximant of it; whereas, on the slower timescale (e.g., every hour), shunt capacitors are configured to minimize the longterm discounted voltage deviations using a deep reinforcement learning algorithm. Extensive numerical tests on a real-world 47- bus distribution network as well as the IEEE 123-bus test feeder using real data corroborate the effectiveness of the novel scheme.

Motivation & Objective

  • Motivate and address voltage fluctuations due to high renewable and EV penetration in distribution grids.
  • Propose a hybrid data- and physics-driven framework that jointly controls capacitors and inverters across two timescales.
  • Learn slow-timescale capacitor configurations via deep reinforcement learning.
  • Compute fast-timescale inverter setpoints using exact AC or linearized power-flow models.
  • Demonstrate effectiveness through extensive simulations on real-world and standard test feeders.

Proposed method

  • Formulate a two-timescale optimization: slow-timescale capacitor on-off decisions learned with deep reinforcement learning (DRL) and fast-timescale inverter reactive power setpoints computed by convex optimization.
  • Use either an exact AC model with SOCP relaxation or a linearized distribution flow model to obtain inverter setpoints.
  • Model capacitor decisions as a Markov decision process and solve with a deep Q-network (DQN) approach enhanced with a target network and experience replay.
  • Represent inverter constraints and capacitor configurations to ensure feasible reactive power support at each timeslot.
  • Incorporate a hyper deep Q-network to cope with the large action space from many capacitors.

Experimental results

Research questions

  • RQ1Can a two-timescale control framework efficiently and effectively regulate bus voltages under stochastic load and generation without full distribution knowledge?
  • RQ2Does slow-timescale DRL for capacitor on-off decisions synergize with fast-timescale inverter optimization to minimize long-term voltage deviations?
  • RQ3How do exact AC-based and linearized power-flow models compare in enabling fast inverter setpoint optimization within the proposed scheme?
  • RQ4Can modifications like target networks and experience replay stabilize DRL in this power-system context?

Key findings

  • The two-timescale scheme can jointly manage capacitors and inverters to reduce voltage deviations in distribution grids.
  • Fast-timescale inverter setpoints can be computed via exact AC-based SOCP or a linearized quadratic program, given the current capacitor configuration.
  • Slow-timescale capacitor decisions are learned through a DRL approach (DRL with a deep Q-network) that accounts for stochastic generation and load.
  • The method employs a target network and experience replay to stabilize learning and improve convergence.
  • The framework is validated through extensive numerical tests on a real-world 47-bus distribution network and the IEEE 123-bus test feeder using real data.
  • The approach addresses the curse of dimensionality in the capacitor action space via a hyper deep Q-network.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.