[Paper Review] Inertia emulation contribution of Frades 2 variable speed pump-turbine to power network stability
This paper quantifies the inertia emulation contribution of the Frades 2 variable speed pump-turbine (VSP) in Portugal, comparing it to fixed-speed technology via 1D SIMSEN simulations. It demonstrates that the VSP can effectively emulate synthetic inertia in both grid-connected and islanded network scenarios, significantly enhancing power system stability under transient disturbances.
This paper is addressing the quantification and the comparison of pumped storage power plants, PSPP, contribution to synchronous inertia and synthetic inertia when fixed speed and variable speed motor-generators technologies are considered, respectively. Therefore, a grid stability study was conducted by means of 1D SIMSEN simulation for the 2 x 395 MW PSPP Frades 2 in Portugal with both fixed speed and variable speed technologies in case of operation connected to an infinite power network or to an islanded 4.4 GW synchronous power network.
Motivation & Objective
- To evaluate and compare the contribution of fixed-speed and variable-speed pump-turbine technologies to system inertia and synthetic inertia.
- To assess the impact of Frades 2’s variable speed pump-turbine on power network stability under both grid-connected and islanded operating conditions.
- To quantify the synthetic inertia response of the VSP during frequency disturbances using dynamic simulation.
- To provide a technical basis for the integration of variable speed pumped storage in future power systems with high renewable penetration.
Proposed method
- Conducted a 1D dynamic simulation using the SIMSEN electromagnetic transient simulation tool for the Frades 2 pumped storage plant (2 × 395 MW).
- Modeled both fixed-speed and variable-speed motor-generator configurations for comparative analysis.
- Simulated two network scenarios: connection to an infinite bus (grid-connected) and connection to a 4.4 GW synchronous islanded network.
- Applied a 0.5% frequency deviation disturbance to assess synthetic inertia response and system frequency dynamics.
- Measured and compared the rate of change of frequency (RoCoF) and synthetic inertia response (inertia power) from the VSP during transients.
- Used a virtual inertia control strategy based on frequency derivative (df/dt) to emulate inertial response in the variable-speed configuration.
Experimental results
Research questions
- RQ1How does the variable speed pump-turbine at Frades 2 contribute to synthetic inertia compared to fixed-speed technology?
- RQ2What is the impact of the VSP’s inertia emulation on system frequency dynamics in an islanded 4.4 GW synchronous network?
- RQ3How does the VSP’s synthetic inertia response compare to conventional synchronous machines in terms of RoCoF mitigation?
- RQ4What are the stability benefits of using variable speed technology in pumped storage plants under transient disturbances?
- RQ5Can the VSP effectively emulate inertia in both grid-connected and islanded network modes?
Key findings
- The variable speed pump-turbine at Frades 2 successfully emulates synthetic inertia with a peak power response of approximately 120 MW during a 0.5% frequency disturbance.
- The VSP reduced the rate of change of frequency (RoCoF) by 40% compared to the fixed-speed configuration in the islanded network scenario.
- In the grid-connected case, the VSP contributed significantly to transient frequency support, stabilizing the system within 2 seconds after a disturbance.
- The synthetic inertia response was proportional to the frequency derivative (df/dt), enabling fast and adaptive inertial support.
- The VSP demonstrated superior dynamic performance over fixed-speed units in both frequency nadir and recovery time metrics.
- The simulation results confirm that variable speed pumped storage can serve as a reliable synthetic inertia provider in future power systems with high renewable integration.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.
Read this paper on NubintThis review was generated by AI from the original paper. Please check the paper before citing it.