[Paper Review] Operations-Based Planning for Placement and Sizing of Energy Storage in a Grid With a High Penetration of Renewables
This paper proposes an operations-based heuristic for optimal placement and sizing of energy storage in transmission grids with high renewable penetration. By simulating an idealized optimal control algorithm across all nodes under perfect forecasts, it identifies critical transmission nodes—not renewable sites—that maximize controllability over network congestion, reducing required storage capacity by up to 30% compared to conventional placements.
As the penetration level of transmission-scale time-intermittent renewable generation resources increases, control of flexible resources will become important to mitigating the fluctuations due to these new renewable resources. Flexible resources may include new or existing synchronous generators as well as new energy storage devices. The addition of energy storage, if needed, should be done optimally to minimize the integration cost of renewable resources, however, optimal placement and sizing of energy storage is a difficult optimization problem. The fidelity of such results may be questionable because optimal planning procedures typically do not consider the effect of the time dynamics of operations and controls. Here, we use an optimal energy storage control algorithm to develop a heuristic procedure for energy storage placement and sizing. We generate many instances of intermittent generation time profiles and allow the control algorithm access to unlimited amounts of storage, both energy and power, at all nodes. Based on the activity of the storage at each node, we restrict the number of storage node in a staged procedure seeking the minimum number of storage nodes and total network storage that can still mitigate the effects of renewable fluctuations on network constraints. The quality of the heuristic is explored by comparing our results to seemingly "intuitive" placements of storage.
Motivation & Objective
- Address the growing challenge of integrating time-intermittent renewable generation into transmission networks without increasing operational risk.
- Overcome the limitations of traditional planning that decouples expansion and operational planning, especially under high renewable penetration.
- Develop a heuristic for optimal energy storage placement and sizing that accounts for dynamic network constraints and real-time control effects.
- Minimize total storage capacity (power and energy) while maintaining system security under fluctuating renewable generation.
- Identify network nodes with high controllability—capable of redirecting or mitigating renewable-induced congestion—beyond obvious choices like renewable buses.
Proposed method
- Simulate an optimal energy storage control algorithm using perfect renewable forecasts across all network nodes.
- Run multiple time-series simulations of intermittent renewable generation to generate statistics on storage activity at each node.
- Use the simulated storage activity to rank nodes by their contribution to mitigating network constraint violations.
- Apply a staged node-reduction heuristic to identify the minimal set of storage-enabled nodes that maintain system performance.
- Compare results against intuitive placements (e.g., at renewable buses) and unrestricted storage scenarios.
- Analyze network flows and storage injection patterns to explain why certain transmission nodes outperform others.
Experimental results
Research questions
- RQ1Which network nodes provide the highest controllability over congestion caused by fluctuating renewable generation?
- RQ2Does optimal storage placement favor renewable generation buses or strategic transmission nodes?
- RQ3Can a heuristic based on simulated optimal control activity identify a minimal set of storage nodes that maintain system security?
- RQ4How does the performance of the heuristic compare to intuitive storage placement strategies?
- RQ5To what extent can controlled power injections at key nodes redirect renewable fluctuations to regions with higher mitigation capacity?
Key findings
- The optimal storage placement does not favor renewable generation buses; instead, it identifies two critical transmission nodes as most effective.
- The two-node set achieved comparable or better constraint violation mitigation than the ten-node and unrestricted-node sets, despite having fewer storage points.
- Beyond 30% renewable penetration, the two-node set required significantly less total network power and energy capacity than the ten-node or unrestricted cases.
- The two-node set reduced required storage capacity by up to 30% compared to the unrestricted case, indicating superior controllability.
- The two nodes are located at key transmission bottlenecks between major system regions, enabling dynamic rerouting of renewable power flows.
- Control at these nodes allows redirection of renewable fluctuations to regions with greater inherent flexibility, enhancing system-wide mitigation capacity.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.