[Paper Review] A Generalized-Impedance Based Stability Criterion for Three-Phase Grid-Connected Voltage Source Converters

Huanhai Xin, Ziheng Li|arXiv (Cornell University)|Mar 30, 2017
Microgrid Control and OptimizationEngineering5 references5 citations
TL;DR

This paper proposes a generalized-impedance based stability criterion for three-phase grid-connected voltage source converters (VSCs) that accurately handles coupling terms in the impedance matrix by transforming the multi-input-multi-output (MIMO) system into an equivalent single-input-single-output (SISO) framework via generalized impedances. The method enables precise stability assessment without approximating coupling terms, and the study demonstrates the impact of phase-locked loop (PLL) parameters on system stability, validated through hardware-in-the-loop (HIL) simulation on RT-LAB.

ABSTRACT

The output impedance matrices of three-phase grid-connected voltage source converters (VSCs) are widely used in power system stability analysis. Regardless of how the impedance is modeled, there always exist coupling terms in the impedance matrix, which makes the system a multi-input- multi-output (MIMO) system. Some approximation approaches omit the coupling terms so that a three-phase system can be treated like a single-phase one, and the impedance-based stability criterion for a single-input-single-output (SISO) system is applicable. However, such handling may result in analytical errors or even incorrect conclusions in a mirror frequency coupled system. By introducing the concept of generalized- impedances, this letter proposes a new stability criterion based on a virtual SISO system, which can effectively handle the coupling terms. Further, the effects of the phase-locked-loop (PLL) parameters on system stability are studied based on the proposed criterion. The effectiveness of the proposed criterion is verified by a hardware-in-the-loop (HIL) simulation based on RT-LAB.

Motivation & Objective

  • To address the limitations of conventional impedance-based stability analysis in three-phase grid-connected VSCs, where coupling terms in the impedance matrix complicate MIMO system analysis.
  • To overcome the inaccuracies introduced by approximating coupling terms as if the system were single-phase (SISO), which can lead to incorrect stability conclusions in mirror-frequency coupled systems.
  • To develop a generalized-impedance framework that enables accurate stability assessment by transforming the MIMO system into an equivalent SISO system while preserving coupling effects.
  • To investigate the influence of phase-locked loop (PLL) parameters on system stability using the proposed criterion.

Proposed method

  • Introduces the concept of generalized impedance to represent the effective impedance seen by each sequence component in the dq-frame, enabling decoupled analysis of the MIMO system.
  • Transforms the three-phase VSC system into an equivalent SISO system using generalized impedances, thereby allowing application of standard SISO stability criteria.
  • Derives the generalized impedance matrix by analyzing the small-signal model of the VSC in the dq reference frame, accounting for all coupling terms explicitly.
  • Applies the Nyquist stability criterion to the equivalent SISO system defined by the generalized impedance to assess system stability.
  • Performs eigenvalue analysis and stability margin evaluation based on the generalized impedance to quantify system robustness.
  • Validates the proposed criterion using hardware-in-the-loop (HIL) simulation on the RT-LAB platform under various PLL parameter settings.

Experimental results

Research questions

  • RQ1How can the coupling terms in the impedance matrix of a three-phase grid-connected VSC be accurately handled without approximating the system as single-phase?
  • RQ2What is the impact of phase-locked loop (PLL) parameters on the stability of a three-phase VSC when coupling effects are preserved in the analysis?
  • RQ3Can a generalized-impedance framework effectively transform a MIMO VSC system into an equivalent SISO system for stability assessment?
  • RQ4Does the proposed criterion yield more accurate stability conclusions than conventional SISO approximations in mirror-frequency coupled systems?
  • RQ5How does the proposed method compare with traditional impedance-based analysis in terms of accuracy and robustness under varying system parameters?

Key findings

  • The proposed generalized-impedance based criterion accurately captures the stability behavior of three-phase VSCs without neglecting coupling terms, avoiding analytical errors from SISO approximations.
  • The method reveals that PLL parameters significantly influence system stability, particularly through their impact on the positive and negative sequence impedance interactions.
  • HIL simulation results confirm that the proposed criterion correctly predicts stability margins and identifies instability under conditions where conventional methods may fail.
  • The generalized impedance framework enables a clear interpretation of stability margins in terms of phase and gain margins, similar to SISO systems.
  • The study demonstrates that mirror-frequency coupling effects are critical and must be preserved in stability analysis, as their omission leads to misleading conclusions.
  • The validation on RT-LAB shows strong consistency between theoretical predictions and real-time simulation results, confirming the practical applicability of the proposed criterion.

Read this paper