Skip to main content
QUICK REVIEW

[Paper Review] Adaptive Optimal PMU Placement Based on Empirical Observability Gramian

Junjian Qi, Kai Sun|arXiv (Cornell University)|Nov 25, 2014
Power System Optimization and StabilityEngineering38 references7 citations
TL;DR

This paper proposes an adaptive optimal PMU placement method that dynamically selects between the determinant, trace, minimum eigenvalue, and condition number of the empirical observability gramian as the objective function based on PMU count. It shows that for low PMU counts (e.g., <10), the minimum eigenvalue and condition number yield better observability and estimation performance than the determinant, which is validated on the NPCC 48-machine system using a square-root unscented Kalman filter with significantly reduced estimation errors and higher convergence rates.

ABSTRACT

In this paper, we compare four measures of the empirical observability gramian, including the determinant, the trace, the minimum eigenvalue, and the condition number, which can be used to quantify the observability of system states and to obtain the optimal PMU placement for power system dynamic state estimation. An adaptive optimal PMU placement method is proposed by automatically choosing proper measures as the objective function. It is shown that when the number of PMUs is small and thus the observability is very weak, the minimum eigenvalue and the condition number are better measures of the observability and are preferred to be chosen as the objective function. The effectiveness of the proposed method is validated by performing dynamic state estimation on an Northeast Power Coordinating Council (NPCC) 48-machine 140-bus system with the square-root unscented Kalman filter.

Motivation & Objective

  • To address the lack of systematic, quantitative observability metrics for optimal PMU placement in dynamic state estimation (DSE), especially under low PMU counts.
  • To compare multiple measures of the empirical observability gramian—determinant, trace, minimum eigenvalue, and condition number—for their effectiveness in quantifying system observability.
  • To develop an adaptive OPP method that automatically selects the most suitable gramian measure based on the number of PMUs to maximize observability and estimation accuracy.
  • To validate the proposed method on a large-scale power system (NPCC 48-machine, 140-bus) using dynamic state estimation with a square-root unscented Kalman filter.

Proposed method

  • The empirical observability gramian is computed from the system's state transition and output functions under typical operating conditions, capturing the degree of state observability for a given PMU configuration.
  • Four measures—determinant, trace, minimum eigenvalue (σ_min), and condition number (κ)—are evaluated as potential objective functions for optimal PMU placement (OPP).
  • An adaptive selection rule is designed: for PMU counts ≥10, the determinant is used; for lower counts, the condition number (−κ) is preferred over σ_min due to superior performance improvement.
  • The OPP problem is solved using derivative-free optimization (NOMAD and OPTI toolboxes), with dynamic state estimation performed via the square-root unscented Kalman filter on a 5-second trajectory with a three-phase fault.
  • The method evaluates performance using average rotor angle estimation error and the number of convergent states (within 2% error in the last second).
  • The adaptive strategy dynamically switches objective functions based on the magnitude of the determinant (log det ≥ 0) to ensure numerical stability and observability robustness.

Experimental results

Research questions

  • RQ1Which measure of the empirical observability gramian—determinant, trace, minimum eigenvalue, or condition number—most reliably quantifies system observability in dynamic state estimation under low PMU counts?
  • RQ2How does the performance of optimal PMU placement vary when using different gramian measures, particularly in terms of estimation error and convergence of state variables?
  • RQ3Can an adaptive selection strategy that switches between different gramian measures based on PMU count improve overall observability and estimation accuracy compared to using a single fixed measure?
  • RQ4To what extent does the proposed adaptive OPP method reduce estimation error and increase the number of convergent states in dynamic state estimation on a large-scale power system?

Key findings

  • For low PMU counts (<10), the minimum eigenvalue and condition number are more effective than the determinant and trace in quantifying observability, as they yield more stable and meaningful values.
  • The trace is ineffective because it fails to detect zero eigenvalues, which indicate unobservable states.
  • The determinant performs poorly when observability is weak due to its tendency to produce very small values, making it unreliable as a metric under low PMU conditions.
  • The condition number (−κ) outperforms the minimum eigenvalue (σ_min) in improving observability for low PMU counts, justifying its selection as the adaptive objective function.
  • The adaptive OPP method achieves significantly lower average rotor angle estimation error and higher numbers of convergent states compared to random PMU placements.
  • The adaptive method outperforms single-measure OPP strategies, demonstrating superior robustness and accuracy in dynamic state estimation on the NPCC 48-machine, 140-bus system.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.