[Paper Review] Battery Placement on Performance of VAR Controls

Hen‐Geul Yeh, Son Doan|arXiv (Cornell University)|Nov 25, 2013
Microgrid Control and OptimizationEngineering15 references4 citations
TL;DR

This paper investigates how battery placement affects VAR control performance in radial distribution networks with photovoltaic (PV) integration. Using dynamic global and local control algorithms to minimize daily power losses, simulations show that rear battery placement reduces voltage variation by up to 13% and improves energy savings by 15% compared to front placement, especially under medium to high PV penetration levels.

ABSTRACT

Battery's role in the development of smart grid is gaining greater attention as an energy storage device that can be integrated with a Photovoltaic (PV) cell in the distribution circuit. As more PVs are connected to the system, real power injection to the distribution can cause fluctuation in the voltage. Due to the rapid fluctuation of the voltage, a more advanced volt-ampere reactive (VAR) power control scheme on a fast time scale is used to minimize the voltage deviation on the distribution. Employing both global and local dynamic VAR control schemes in our previous work, we show the effects of battery placement on the performance of VAR controls in the example of a single branch radial distribution circuit. Simulations verify that having battery placement at the rear in the distribution circuit can provide smaller voltage variations and higher energy savings than front battery placement when used with dynamic VAR control algorithms.

Motivation & Objective

  • To evaluate the impact of battery placement—front versus rear—on voltage regulation and energy efficiency in distribution systems with high PV penetration.
  • To address the challenge of voltage fluctuations caused by rapid PV output changes due to cloud cover and load variations.
  • To compare the performance of global and local dynamic VAR control algorithms under different battery placement strategies.
  • To quantify energy savings and voltage variation reduction across low, medium, and high PV penetration levels.
  • To provide actionable insights for utility incentives targeting rear-node battery installations to improve grid stability.

Proposed method

  • Model a single radial distribution circuit with 30 buses, where the substation is at the front (bus 0) and the end of the line is at the rear (bus 30).
  • Formulate a day-long optimization problem to minimize total active power losses using both global and local dynamic VAR control algorithms.
  • Integrate battery systems with PV inverters at either the front or rear of the circuit, enabling fast reactive power support via inverters and battery charge/discharge control.
  • Use discrete time steps (e.g., hourly or 20-minute intervals) to simulate real-time voltage and power flow dynamics under varying solar generation and load conditions.
  • Apply control variables including battery charge/discharge rate (βj(t)) and inverter reactive power output (qjg(t)) to regulate voltage and reduce losses.
  • Compare results across three PV penetration levels (20%, 50%, 80%) and different inverter size constraints (smax = 1.1, 1.3, 1.5).

Experimental results

Research questions

  • RQ1How does rear battery placement compare to front battery placement in reducing voltage variation across a radial distribution feeder?
  • RQ2What is the impact of battery placement on energy savings when using dynamic global and local VAR control algorithms?
  • RQ3How do voltage variations and power losses change under low, medium, and high PV penetration levels with different battery placements?
  • RQ4Can dynamic control algorithms effectively regulate voltage at the rear of the feeder when batteries are placed at the front versus the rear?
  • RQ5What is the optimal placement strategy for battery-PV systems to maximize voltage regulation and energy efficiency in distribution networks?

Key findings

  • Rear battery placement reduces peak voltage variation by approximately 12% compared to front placement at 20% PV penetration (a=0.2, smax=1.1).
  • At 50% PV penetration (a=0.5, smax=1.1), rear battery placement reduces peak voltage variation by 13% and average variation by 9% compared to front placement.
  • Energy savings from rear battery placement reach 15% at medium PV penetration (a=0.5), compared to front placement, under the same inverter size constraints.
  • The global control algorithm achieves better voltage regulation and energy savings than local control across all PV penetration levels and battery placements.
  • Voltage variation increases toward the rear of the feeder when no control is applied, but is significantly mitigated when batteries are placed at the rear.
  • Battery placement at the rear enables better utilization of both active power from PV and reactive power support from inverters to regulate voltage at remote nodes.