[Paper Review] Coordinating Power Grid Frequency Regulation Service with Data Center Load Flexibility

Ali Jahanshahi, Sara Rashidi Golrouye|arXiv (Cornell University)|Jan 30, 2026
Cloud Computing and Resource ManagementComputer Science0 citations
TL;DR

The paper introduces Exogenous Carbon and EcoCenter, a framework that coordinates GPU data centers with power grids to provide frequency regulation while reducing grid-side carbon emissions.

ABSTRACT

AI/ML data center growth have led to higher energy consumption and carbon emissions. The shift to renewable energy and growing data center energy demands can destabilize the power grid. Power grids rely on frequency regulation reserves, typically fossil-fueled power plants, to stabilize and balance the supply and demand of electricity. This paper sheds light on the hidden carbon emissions of frequency regulation service. Our work explores how modern GPU data centers can coordinate with power grids to reduce the need for fossil-fueled frequency regulation reserves. We first introduce a novel metric, Exogenous Carbon, to quantify grid-side carbon emission reductions resulting from data center participation in regulation service. We additionally introduce EcoCenter, a framework to maximize the amount of frequency regulation provision that GPU data centers can provide, and thus, reduce the amount of frequency regulation reserves necessary. We demonstrate that data center participation in frequency regulation can result in Exogenous carbon savings that oftentimes outweigh Operational carbon emissions.

Motivation & Objective

  • Quantify grid-side carbon emission reductions from data center frequency regulation participation using a new Exogenous Carbon metric.
  • Develop EcoCenter to maximize frequency regulation provision from GPU data centers.
  • Address the limitations of CPU-only and prior GPU regulation approaches by leveraging GPU power flexibility and co-located workloads.
  • Model how data center regulation interacts with grid operations and regulation reserves to unveil hidden emissions.
  • Demonstrate the potential benefits of coordinated data center participation for grid stability and renewable integration.

Proposed method

  • Define C_op and C_op_w/RS to include Exogenous Carbon as the reduction in grid emissions when data centers provide regulation reserves.
  • Develop a grid-aware unit commitment modeling approach to obtain MCE_resv by comparing grid emissions with and without data center regulation service.
  • Propose EcoCenter to maximize R_DC by coordinating GPU DVFS, core allocation, and multi-GPU load assignment in co-located LC and BE workloads.
  • Design and implement a GPU-centric power modulation policy combining power capping and core allocation to achieve high-precision regulation following a 2-second signal.
  • Integrate EcoCenter into containerized (Docker) environments with a Controller, Workload Monitor, Power Monitor, and Resource Manager.
  • Characterize power modulation knobs for GPUs and optimize the policy to maintain workload QoS while achieving regulation targets.

Experimental results

Research questions

  • RQ1How does data center participation in frequency regulation affect grid-side carbon emissions when accounting for hidden emissions of regulation reserves?
  • RQ2What framework and control strategies (EcoCenter) can maximize frequency regulation provision from GPU data centers without sacrificing workload QoS?
  • RQ3How can GPU power modulation knobs (power cap and core allocation) be combined to meet 2-second regulation signals effectively?
  • RQ4What is the impact of co-locating latency-critical and best-effort workloads on achievable regulation provision and grid benefits?

Key findings

  • Exogenous Carbon captures grid-side carbon emission reductions from data center regulation participation, quantifying benefits beyond traditional grid carbon intensity metrics.
  • EcoCenter enables GPU data centers to provide larger frequency regulation reserves by coordinating GPU DVFS, compute unit scaling, and multi-GPU load assignment.
  • GPU-based regulation can outperform CPU-based approaches in terms of potential regulation provision due to greater power flexibility.
  • Co-locating latency-critical and best-effort workloads expands the dynamic power range and improves regulation responsiveness while maintaining QoS.
  • The framework demonstrates that maximizing regulation provision can yield grid-side exogenous carbon savings that may outweigh operational carbon costs.]
  • The approach presents a path to align data center growth with higher renewable energy penetration by reducing reliance on fossil-fuel regulation reserves.