[Paper Review] Distribution Network Marginal Costs - Part I: A Novel AC OPF Including Transformer Degradation
This paper proposes a novel AC Optimal Power Flow (OPF) model for radial distribution networks that explicitly incorporates transformer degradation as a dynamic, time-coupled cost component in Distribution Locational Marginal Costs (DLMCs). By modeling the incremental loss of life (LoL) from real-time loading and internalizing future degradation into day-ahead DLMCs, the framework enables co-optimization of DERs (PV and EVs) and network operations, improving efficiency and asset longevity beyond traditional uniform pricing models.
This two-part paper considers the day-ahead operational planning problem of a radial distribution network hosting Distributed Energy Resources (DERs) including Solar Photovoltaic (PV) and storage-like loads such as Electric Vehicles (EVs). We estimate dynamic Distribution nodal Location Marginal Costs (DLMCs) of real and reactive power and employ them to co-optimize distribution network and DER schedules. In Part I, we develop a novel AC Optimal Power Flow (OPF) model encompassing transformer degradation as a short-run network variable cost, and we decompose real/reactive power DLMCs into additive marginal cost components related to (i) the costs of real/reactive power transactions at the T&D interface/substation, (ii) real/reactive power marginal losses, (iii) voltage and (iv) ampacity congestion, and (v) a new transformer degradation marginal cost component. Our detailed transformer degradation model captures the impact of incremental transformer loading during a specific time period, not only on its Loss of Life (LoL) during that period, but also during subsequent time periods. To deal with this phenomenon, we develop methods that internalize the marginal LoL occurring beyond the daily horizon into the DLMCs evaluated within this horizon. In Part II, we use real distribution feeders to exemplify the use of DLMCs as financial incentives that convey sufficient information to optimize Distribution Network, and DER (PV and EV) operation.
Motivation & Objective
- To address the lack of dynamic, intertemporally consistent cost modeling in distribution network operations, particularly for DERs like PV and EVs.
- To develop a comprehensive framework for Distribution Locational Marginal Costs (DLMCs) that includes not only traditional components like losses and congestion, but also transformer degradation.
- To internalize the marginal loss of life (LoL) from transformer loading beyond the day-ahead horizon into the DLMCs evaluated within the horizon.
- To enable efficient co-optimization of distribution network and DER (PV and EV) schedules using economically efficient, dynamic DLMCs.
Proposed method
- Develops a detailed transformer thermal aging model based on IEEE C.57.91-2011 and IEC 60076-7:2018, tracking hottest-spot temperature (HST) and LoL over time.
- Uses difference equations to model hourly HST and LoL dynamics, enabling integration into a day-ahead AC OPF with high temporal resolution.
- Derives first-order Taylor approximations for non-linear terms in HST and LoL equations to linearize the degradation cost component for optimization.
- Decomposes DLMCs into five additive components: T&D interface costs, loss costs, voltage and ampacity congestion, and a new transformer degradation cost.
- Internalizes future LoL beyond the day-ahead horizon by embedding the marginal degradation cost of current loading into the current DLMC.
- Employs a recursive formulation for HST and LoL using load ratio $ l_t/l^N $, enabling real-time cost tracking and optimization.
Experimental results
Research questions
- RQ1How can transformer degradation be modeled as a dynamic, time-coupled cost in a day-ahead AC OPF for distribution networks?
- RQ2What is the impact of internalizing future loss of life (LoL) from current loading into day-ahead DLMCs on DER scheduling efficiency?
- RQ3How do DLMCs that include transformer degradation compare to traditional uniform pricing in co-optimizing PV and EV operations?
- RQ4What is the structure of the marginal cost decomposition for real and reactive power, including the new degradation component?
- RQ5How can the intertemporal effects of transformer loading be captured in a computationally tractable way for distribution network optimization?
Key findings
- The proposed AC OPF model successfully incorporates transformer degradation as a dynamic, time-coupled cost component in DLMCs, enabling accurate reflection of long-term asset impacts in day-ahead scheduling.
- The marginal degradation cost is internalized into the day-ahead horizon by modeling the incremental loss of life from current loading, even when the degradation occurs in future periods.
- The model decomposes DLMCs into five distinct components: T&D interface costs, loss costs, voltage and ampacity congestion, and a new, quantifiable transformer degradation cost.
- Using Taylor approximations, the non-linear HST and LoL dynamics are linearized, enabling efficient integration into a mixed-integer second-order cone program (MISOCP) for optimization.
- The framework enables co-optimization of DERs (PV and EVs) and network operations, reducing overloading risks and extending transformer life.
- The model demonstrates that ignoring transformer degradation in DLMCs leads to suboptimal scheduling, potentially causing premature aging and costly replacements, as seen in real-world estimates (e.g., $7,400 per transformer replacement).