[Paper Review] Distribution Network Marginal Costs -- Part II: Case Study Based Numerical Findings
This paper proposes a novel AC Optimal Power Flow (OPF) model that incorporates dynamic Distribution Locational Marginal Costs (DLMCs) accounting for transformer degradation, reactive power support, and real-time network constraints. Through case studies on actual distribution feeders, it demonstrates that DLMC-based scheduling significantly improves DER hosting capacity, reduces infrastructure investment needs, and outperforms conventional methods like Time-of-Use and loss minimization by internalizing short-term marginal asset costs.
This two-part paper considers the day-ahead operational planning problem of a radial distribution network hosting Distributed Energy Resources (DERs), such as Solar Photovoltaic (PV) and Electric Vehicles (EVs). In Part I, we develop a novel AC Optimal Power Flow (OPF) model that estimates dynamic Distribution nodal Location Marginal Costs (DLMCs) of real and reactive power including transformer degradation. These all-inclusive DLMCs are key in the co-optimization of the distribution network and DER schedules. Part II discusses the implication of using DLMCs to represent the benefit of shifting real/reactive power across time and achieve optimal Distribution Network and DER operation. Moreover, it evaluates, elaborates and analyzes the novel AC OPF through extensive numerical results of actual distribution feeder-based case studies involving a wealth of future EV and PV adoption scenarios. Optimal schedules are compared to schedules that rely on apparently reasonable approaches, namely Business as Usual (i.e., do nothing), Time of Use, and traditional line loss minimization. The overwhelming evidence of extensive numerical results supports the significant benefits of internalizing short-run marginal asset - primarily transformer - degradation. Apart from optimal short-run scheduling, the proposed approach can harvest otherwise idle DER (PV/EV) reactive power compensation capabilities, increase distribution network DER (PV/EV) hosting capacity, and mitigate investments in distribution infrastructure that would be otherwise required to support distribution utilities' obligation to serve. Finally, numerical evidence on the benefits of AC OPF modeling intertemporal transformer life degradation suggests that it may be worth considering the introduction of intra-day markets.
Motivation & Objective
- To develop a comprehensive framework for dynamic Distribution Locational Marginal Costs (DLMCs) that include transformer degradation and reactive power impacts.
- To evaluate the effectiveness of DLMCs in enabling optimal co-scheduling of distribution networks and Distributed Energy Resources (DERs) such as PV and EVs.
- To compare DLMC-based scheduling against conventional approaches—Business as Usual, Time-of-Use, and line loss minimization—using real feeder data.
- To demonstrate how DLMCs can unlock idle reactive power capabilities of DERs and reduce the need for costly network upgrades.
Proposed method
- Develops an AC Optimal Power Flow (OPF) model that explicitly captures intertemporal transformer degradation through dynamic cost functions.
- Derives spatiotemporal DLMCs as sensitivity measures of system cost to changes in real and reactive power injections at each bus and time period.
- Uses sensitivity analysis via linearized power flow equations to unbundle DLMC components into contributions from voltage limits, ampacity, and transformer aging.
- Applies the DLMC framework to actual radial distribution feeders under diverse future scenarios of PV and EV penetration.
- Employs a two-part tariff mechanism to test whether DLMC-based prices can support optimal DER self-scheduling while ensuring revenue adequacy.
- Conducts extensive numerical experiments comparing DLMC-based scheduling against business-as-usual, TOU, and loss-minimization strategies.
Experimental results
Research questions
- RQ1How do DLMCs based on AC OPF with transformer degradation improve the efficiency of distribution network and DER operation compared to conventional methods?
- RQ2To what extent can DLMCs unlock unused reactive power support from PV and EVs, thereby increasing hosting capacity?
- RQ3What is the impact of internalizing short-run marginal transformer degradation on network investment decisions and operational cost?
- RQ4Can DLMC-based pricing signals lead to smooth, stable, and ratepayer-acceptable dynamic tariffs that support optimal scheduling?
- RQ5Is there sufficient economic justification for introducing intra-day markets based on intertemporally coupled DLMCs?
Key findings
- DLMC-based scheduling significantly outperforms Business as Usual, Time-of-Use, and line loss minimization in reducing network congestion and operational costs across all tested scenarios.
- Internalizing transformer degradation in DLMCs leads to a measurable reduction in required distribution infrastructure upgrades, even under high PV and EV penetration levels.
- Voltage and ampacity constraints alone are insufficient to generate optimal price signals; including transformer degradation is essential for system-wide efficiency.
- The proposed method fully leverages idle reactive power capabilities of DERs, increasing the effective hosting capacity for PV and EVs without additional network upgrades.
- DLMC profiles are smooth and stable across time and location, suggesting that DLMC-based dynamic pricing is feasible and unlikely to provoke ratepayer resistance.
- Numerical results provide strong evidence that intra-day markets based on intertemporal DLMCs could improve system efficiency and merit further exploration.
Read this paper
Open the full text in the Nubint reader and ask about any passage as you read.
Read this paper on NubintThis review was generated by AI from the original paper. Please check the paper before citing it.