[Paper Review] Effects of current limit for grid forming converters on transient stability: analysis and solution
This paper identifies that current limiting in grid-forming converters (GFCs) can severely compromise transient stability during large system events like frequency jumps, phase shifts, and voltage dips. It proposes using virtual active power derived from unsaturated current references to maintain synchronization during current limit operation, validated through Power Hardware-in-the-Loop (PHIL) tests showing improved stability margins across multiple transient scenarios.
Grid forming control applied to power converters that interface storage or renewable generation to the power grid, has been identified as a potential solution to facilitate a substantial share of converter-based renewable generation in the power system. Analyzing the response of grid forming converters (GFC) for large frequency, phase, and voltage events, particularly when the GFC enters the current limit operation, is very important for system stability, but studies on this have been limited. This paper presents a quantitative and illustrative analysis of the impact of the current limit in GFC on the transient stability of a system comprising of GFC. Furthermore, a solution based on virtual active power is proposed to improve the transient stability margin of the GFC when the GFC enters the current limit. Finally, the analysis and the proposed method to enhance the transient stability are verified by Power hardware in the loop (PHIL) experimental tests.
Motivation & Objective
- To analyze the impact of current limiting on transient stability in grid-forming converters (GFCs) during large system disturbances such as frequency changes, phase jumps, and voltage dips.
- To identify instability risks arising from the wind-up of power-based synchronization loops when GFCs enter current-limited operation.
- To develop a robust solution that maintains synchronization during current limiting without relying on additional control loops or PLLs.
- To validate the proposed method through Power Hardware-in-the-Loop (PHIL) experiments on both an infinite bus system and a modified IEEE-9 bus system with low inertia.
Proposed method
- The paper conducts a quantitative transient stability analysis of GFCs under three major events: large frequency changes (RoCoF), phase jumps, and voltage dips, with current limiting enabled.
- A virtual active power signal is derived from the unsaturated current reference, replacing measured active power in the synchronization loop during current-limited operation.
- The method avoids reliance on external phase-locked loops (PLLs) or complex parameter tuning, ensuring seamless transition into and out of current limit.
- The GFC control is implemented on an FPGA-based digital controller with trapezoidal integration and 40 µs sampling, using proportional inner current control with current limiting.
- PHIL experiments are conducted using RTDS real-time simulation and a physical VSC hardware interface, with signal scaling and low-pass filtering (250 µs) to ensure stability.
- The system is tested on both an infinite bus model and a modified IEEE-9 bus system with two replaced synchronous generators, simulating a low-inertia future grid.
Experimental results
Research questions
- RQ1How does current limiting in grid-forming converters affect transient stability during large frequency disturbances?
- RQ2What causes synchronization loss in GFCs when they enter current-limited operation during phase jump or voltage dip events?
- RQ3Can a virtual active power signal derived from unsaturated current references maintain synchronization during current limiting without additional control loops?
- RQ4How does the proposed method compare to conventional measured active power-based synchronization under current-limited conditions?
- RQ5To what extent does the proposed solution improve transient stability margins across different types of system events?
Key findings
- When using measured active power for synchronization, GFCs lose synchronism during large disturbances such as VSC1 disconnection in a low-inertia system, especially at low power setpoints and with 5% P-f droop.
- The proposed virtual active power method enables seamless entry into and exit from current limiting, maintaining synchronization under all tested transient events.
- PHIL results for the infinite bus case show excellent agreement between simulation analysis and experimental validation for RoCoF, phase jump, and fault events.
- In the modified IEEE-9 system, the GFC with virtual power maintains synchronism during a 100 MW generation disconnection event, while the conventional method fails.
- The method improves transient stability margins without requiring additional control structures or PLL backup, enhancing robustness and reliability.
- The use of virtual power ensures stable operation even when the actual active power feedback is saturated due to current limiting, preventing wind-up in the synchronization loop.