Skip to main content
QUICK REVIEW

[Paper Review] Enhancing Distribution Resilience with Mobile Energy Storage: A Progressive Hedging Approach

Jip Kim, Yury Dvorkin|arXiv (Cornell University)|Mar 3, 2018
Electric Vehicles and InfrastructureEngineering12 references4 citations
TL;DR

This paper proposes a two-stage stochastic optimization model using progressive hedging to jointly plan mobile energy storage (ES) unit investments and their dynamic relocation during disasters, significantly reducing load shedding and operating costs compared to stationary or no ES. The method enables spatial flexibility to enhance distribution system resilience while maintaining economic efficiency under uncertainty.

ABSTRACT

Electrochemical energy storage (ES) units (e.g. batteries) have been field-validated as an efficient back-up resource that enhance resilience of the distribution system in case of natural disasters. However, using these units for resilience is not sufficient to economically justify their installation and, therefore, these units are often installed in locations where they incur the greatest economic value during normal operations. Motivated by the recent progress in transportable ES technologies, i.e. ES units can be moved using public transportation routes, this paper proposes to use this spatial flexibility to bridge the gap between the economically optimal locations during normal operations and disaster-specific locations where extra back-up capacity is necessary. We propose a two-stage optimization model that optimizes investments in mobile ES units in the first stage and can re-route the installed mobile ES units in the second stage to avoid the expected load shedding caused by disaster forecasts. Since the proposed model cannot be solved efficiently with off-the-shelf solvers, even for relatively small instances, we apply a progressive hedging algorithm. The proposed model and progressive hedging algorithm are tested through two illustrative examples on a 15-bus radial distribution test system.

Motivation & Objective

  • To address the gap between economically optimal ES locations during normal operations and disaster-specific needs.
  • To develop a two-stage stochastic mixed-integer program that models mobile ES unit relocation as binary recourse decisions.
  • To enable cost-effective resilience enhancement by leveraging the spatial mobility of ES units.
  • To overcome computational intractability of binary recourse problems via the progressive hedging algorithm.
  • To demonstrate the superiority of mobile over stationary or no ES in reducing load shedding and operational costs.

Proposed method

  • Formulates a two-stage stochastic mixed-integer program where the first stage selects mobile ES investment locations and sizes, and the second stage determines optimal relocation and dispatch under disaster scenarios.
  • Models mobile ES unit relocation as binary decisions (1 = moved, 0 = not moved), capturing spatial flexibility in response to forecasted disasters.
  • Applies the progressive hedging (PH) algorithm to solve the computationally challenging problem by iteratively penalizing deviations from consensus first-stage decisions across scenarios.
  • Uses scenario decomposition to optimize first- and second-stage decisions independently per scenario, with penalty-based consensus enforcement.
  • Implements the PH algorithm with an exogenous penalty coefficient to converge to a solution satisfying the non-anticipativity constraint.
  • Validates the model on a 15-bus radial distribution system with two case studies under different disaster scenario sets.

Experimental results

Research questions

  • RQ1How can mobile energy storage units be optimally invested and relocated to enhance distribution system resilience during natural disasters?
  • RQ2What is the impact of mobile ES unit mobility on reducing load shedding and operational costs compared to stationary or no ES?
  • RQ3Can the progressive hedging algorithm effectively solve the two-stage stochastic mixed-integer program with binary recourse decisions for mobile ES planning?
  • RQ4How do different disaster scenario sets affect the optimal routing and dispatch of mobile ES units?
  • RQ5What is the trade-off between economic efficiency during normal operations and resilience during disasters when using mobile ES?

Key findings

  • In Case 1, mobile ES units reduced load shedding compared to the no-ES case, with the unit relocating from bus 1 to bus 4 at t=6 to supply downstream buses 5 and 6 until t=24.
  • In Case 2 with five disaster scenarios, mobile ES units achieved the lowest total load shedding and operating cost, outperforming both no-ES and stationary-ES configurations.
  • The optimal mobile ES placement during normal operations was at bus 1, but it was relocated to different buses (e.g., 4, 5, 6) depending on the scenario, demonstrating dynamic routing flexibility.
  • The progressive hedging algorithm successfully solved the problem, converging to a solution that balanced cost and resilience across all disaster scenarios.
  • The mobile ES unit’s state-of-charge (SoC) was dynamically managed across time intervals, with values ranging from 0.3 to 1.0 MWh, and transit states marked as 'T' in the routing trajectory.
  • The model showed that mobile ES units can be strategically repositioned to avoid load shedding even when disasters affect multiple lines, highlighting their value in complex, multi-scenario disaster planning.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.