Skip to main content
QUICK REVIEW

[Paper Review] Experimental implementation of an emission-aware prosumer with online flexibility quantification and provision

Hanmin Cai, Philipp Heer|arXiv (Cornell University)|Oct 25, 2021
Building Energy and Comfort OptimizationEngineering37 references6 citations
TL;DR

This study presents an emission-aware prosumer system using model predictive control (MPC) to minimize carbon emissions from electricity imports while enabling online flexibility quantification and provision to a distribution system operator (DSO). In a real-world building experiment, the system achieved a 12.5% reduction in equivalent carbon emissions compared to a PV self-consumption benchmark, with no rebound effects and maintained thermal comfort.

ABSTRACT

Active building energy management holds potential to reduce global energy-related emissions and support flexible operations of future low-carbon systems. This requires to integrate diverse objectives and engage multiple stakeholders. However, there remains a gap in comprehensive field insights into emission reduction, flexibility provision, and user impacts. This study examined how a real occupied building, with all its energy assets, could function as an emission-aware flexible prosumer. An existing building energy management system was enhanced by integrating a model predictive control strategy. The enhanced setup minimized the equivalent carbon emission due to electricity imports and provided flexibility to the energy system. The experimental results indicated an emission reduction of 12.5% compared to a rule-based controller that maximized PV self-consumption. In addition, a minimal flexibility provision experiment was demonstrated with a locally emulated distribution system operator. The results suggested that flexibility was provided without the risk of rebound effects. This is due to the flexibility envelope that was self-reported in advance. The study concluded by highlighting technical challenges in realizing emission reduction and flexibility in practice.

Motivation & Objective

  • To bridge the gap in comprehensive experimental insights on emission-aware building operation, flexibility provision, and occupant impacts in real-world settings.
  • To develop and validate an online flexibility quantification and provision framework that respects user comfort and operational constraints.
  • To assess the practical feasibility of integrating emission reduction, flexibility services, and occupant preferences in a real occupied building.
  • To evaluate the risk of rebound effects during flexibility provision using a self-reported flexibility envelope.
  • To provide empirical data on thermal comfort and user feedback in a real-time, automated building energy management system.

Proposed method

  • Enhanced an existing building energy management system with a model predictive control (MPC) strategy to minimize equivalent carbon emissions from grid imports.
  • Integrated simplified thermal models derived from historical data to represent space heating and domestic hot water (DHW) loads, ensuring computational efficiency.
  • Formulated online flexibility quantification as an optimization problem that dynamically computes the flexibility envelope based on real-time conditions and user preferences.
  • Coordinated behind-the-meter resources—including heat pumps, thermal energy storage, and electric vehicles—through centralized MPC for flexible power modulation.
  • Demonstrated flexibility provision in a closed-loop experiment using an emulated DSO, where flexibility was requested to mitigate network congestion.
  • Used a self-reported flexibility envelope to pre-define operational boundaries, minimizing the risk of rebound effects during flexibility delivery.

Experimental results

Research questions

  • RQ1Can an emission-aware MPC strategy reduce carbon emissions in a real occupied building while maintaining thermal comfort?
  • RQ2How effectively can online flexibility quantification be automated and integrated into real-time building energy management?
  • RQ3What is the risk of rebound effects when providing flexibility to a distribution system operator (DSO) using a self-reported flexibility envelope?
  • RQ4How do occupants perceive thermal comfort and user preferences under automated MPC control in real-world operation?
  • RQ5To what extent can diverse behind-the-meter resources be coordinated to provide measurable and reliable flexibility to the grid?

Key findings

  • The emission-aware MPC reduced equivalent carbon emissions by 12.5% compared to a rule-based controller that maximized photovoltaic (PV) self-consumption.
  • Thermal comfort was maintained throughout the experiment, with 37.5% of survey responses indicating slightly cool conditions in bedrooms, and all DHW feedback rated as 'very satisfied'.
  • No rebound effects were observed during flexibility provision, as the self-reported flexibility envelope ensured that operational limits and user preferences were respected.
  • The online flexibility quantification framework successfully coordinated multiple behind-the-meter resources and enabled automated flexibility provision upon DSO notification.
  • The simplified thermal models, derived from historical data, performed satisfactorily in real-world conditions, likely due to the slow thermal dynamics of water-based ceiling heating.
  • User fatigue during surveys limited feedback collection, indicating a need for improved real-time feedback mechanisms in future deployments.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.