[Paper Review] Frequency Response from Aggregated V2G Chargers With Uncertain EV Connections
This paper proposes a distributionally-robust chance-constrained optimization framework to schedule frequency response (FR) from aggregated vehicle-to-grid (V2G) chargers under uncertain electric vehicle (EV) connection rates. By modeling connection uncertainty via moment-based probabilistic constraints, the method ensures frequency security while enabling V2G to deliver £6,300 annual savings per charger in the GB 2030 system, with value reduced by 20% under 1-second FR delivery delays.
Fast frequency response (FR) is highly effective at securing frequency dynamics after a generator outage in low inertia systems. Electric vehicles (EVs) equipped with vehicle to grid (V2G) chargers could offer an abundant source of FR in future. However, the uncertainty associated with V2G aggregation, driven by the uncertain number of connected EVs at the time of an outage, has not been fully understood and prevents its participation in the existing service provision framework. To tackle this limitation, this paper, for the first time, incorporates such uncertainty into system frequency dynamics, from which probabilistic nadir and steady state frequency requirements are enforced via a derived momeent-based distributionally-robust chance constraint. Field data from over 25,000 chargers is analysed to provide realistic parameters and connection forecasts to examine the value of FR from V2G chargers in annual operation of the the GB 2030 system. The case study demonstrates that uncertainty of EV connections can be effectively managed through the proposed scheduling framework, which results in annual savings of £6,300 or 37.4 tCO2 per charger. The sensitivity of this value to renewable capacity and FR delays is explored, with V2G capacity shown to be a third as valuable as the same grid battery capacity.
Motivation & Objective
- To address the challenge of uncertain EV connection rates in aggregating V2G chargers for frequency response (FR) services.
- To develop a mathematically rigorous scheduling framework that guarantees system frequency security despite stochastic EV availability.
- To quantify the economic and operational value of V2G FR in future low-inertia power systems, particularly under uncertainty.
- To compare V2G FR value against battery storage and assess sensitivity to FR delivery delays and renewable penetration.
Proposed method
- Formulates a distributionally-robust chance-constrained optimization problem using moment-based uncertainty sets for EV connection forecasts.
- Incorporates probabilistic forecasts of net EV connections (mean μᵢ and standard deviation σᵢ) into a stochastic unit commitment model.
- Derives a convex feasible region via moment-based distributionally robust chance constraints to enforce probabilistic bounds on frequency nadir and RoCoF.
- Uses field data from 25,000+ chargers to calibrate realistic connection probability distributions and forecast parameters.
- Integrates the V2G scheduling model into a security-constrained unit commitment (SCUC) framework with dynamic frequency response constraints.
- Applies the model to the GB 2030 system under varying renewable penetration and FR delay scenarios to evaluate performance.
Experimental results
Research questions
- RQ1How can frequency response from aggregated V2G chargers be scheduled when the number of connected EVs is uncertain?
- RQ2What is the impact of EV connection uncertainty on the reliability and economic value of V2G-based frequency response?
- RQ3How does the value of V2G FR compare to equivalent battery storage capacity in terms of cost savings and system security?
- RQ4How do FR delivery delays affect the value of V2G response in securing system frequency?
- RQ5What is the sensitivity of V2G value to renewable capacity and morning connection uncertainty?
Key findings
- The proposed framework enables annual savings of £6,300 or 37.4 tCO₂ per V2G charger in the GB 2030 system by displacing thermal inertia and FR requirements.
- V2G capacity is valued at approximately one-third the value of equivalent battery storage capacity due to lower availability from uncertain EV connections.
- FR delivery delays reduce the value of V2G response by 20% when delays reach 1 second, even with robust scheduling.
- Uncertainty in morning EV plug-in times significantly limits FR availability, especially above 1 GW of V2G capacity, due to high forecast variance (σᵢ).
- The marginal value of V2G saturates at high penetration levels, primarily due to constraints on RoCoF and inertia, not FR availability.
- The difference between deterministic and unimodal constraint results highlights that uncertainty is the second-largest derating factor after average EV connection availability (~42% for domestic, 26% for work).