[Paper Review] Frequency Stability Using MPC-based Inverter Power Control in Low-Inertia Power Systems

Atinuke Ademola-Idowu, Baosen Zhang|arXiv (Cornell University)|Sep 27, 2019
Microgrid Control and OptimizationEngineering29 references7 citations
TL;DR

This paper proposes a Model Predictive Control (MPC)-based Inverter Power Control (MIPC) strategy to optimize active power set-points for inverter-based resources (IBRs) in low-inertia power systems. By explicitly incorporating hard power and energy constraints into a real-time optimization framework with an observer for model mismatch, MIPC significantly outperforms optimally tuned Virtual Synchronous Machines (VSMs), reducing frequency deviation to 0.3 Hz (power-limited) and 0.4 Hz (energy-limited) while maintaining stability under noise, limited communication, and delays.

ABSTRACT

The electrical grid is evolving from a network consisting of mostly synchronous machines to a mixture of synchronous machines and inverter-based resources such as wind, solar, and energy storage. This transformation has led to a decrease in mechanical inertia, which necessitate a need for the new resources to provide frequency responses through their inverter interfaces. In this paper we proposed a new strategy based on model predictive control to determine the optimal active-power set-point for inverters in the event of a disturbance in the system. Our framework explicitly takes the hard constraints in power and energy into account, and we show that it is robust to measurement noise, limited communications and delay by using an observer to estimate the model mismatches in real-time. We demonstrate the proposed controller significantly outperforms an optimally tuned virtual synchronous machine on a standard 39-bus system under a number of scenarios. In turn, this implies optimized inverter-based resources can provide better frequency responses compared to conventional synchronous machines.

Motivation & Objective

  • To address the challenge of frequency instability in low-inertia power systems due to reduced mechanical inertia from increased inverter-based resources (IBRs).
  • To develop a control strategy that explicitly handles hard constraints on IBRs, such as power and energy limits, which are often ignored or poorly managed by conventional methods.
  • To improve frequency regulation performance by optimizing active power set-points in real time using model predictive control (MPC), rather than tuning controller parameters.
  • To ensure robustness against measurement noise, limited communication, and time delays through an observer-based state estimation mechanism.

Proposed method

  • Formulates the inverter power control problem as a finite-horizon optimization using MPC to minimize frequency deviation and rate of change of frequency (ROCOF).
  • Explicitly incorporates hard constraints on active power output and available energy into the optimization problem to prevent infeasible control actions.
  • Uses a state observer to estimate model mismatches and unmeasured system states in real time, enhancing robustness to noisy measurements and incomplete communication.
  • Applies a receding horizon approach: at each time step, the controller solves the optimization problem over a prediction horizon and implements only the first control action.
  • Integrates wide-area measurements when available, and maintains performance even when only partial or delayed measurements are accessible.
  • Employs a dual-layer control structure: local inverter control based on predicted system dynamics, with observer feedback to correct for uncertainty.

Experimental results

Research questions

  • RQ1Can MPC-based inverter control outperform conventional VSM control in minimizing frequency deviation and ROCOF in low-inertia systems with hard constraints?
  • RQ2How does the inclusion of explicit power and energy constraints in the MPC optimization improve system stability and performance compared to unconstrained or threshold-based approaches?
  • RQ3To what extent can the MIPC controller maintain performance under noisy measurements, limited communication, and time delays in a real-time control setting?
  • RQ4Can an observer-based state estimation strategy effectively compensate for model mismatch and unmeasured disturbances in a decentralized inverter control framework?

Key findings

  • The MIPC controller reduces frequency deviation to approximately 0.3 Hz under power-limited conditions and 0.4 Hz under energy-limited conditions, significantly outperforming the optimally tuned VSM.
  • The MIPC maintains stable frequency response without rapid oscillations, unlike the VSM, which exhibits pronounced oscillations due to its inability to handle hard constraints explicitly.
  • The controller demonstrates robustness to measurement noise, maintaining smooth and stable performance even at a worst-case SNR of 30 dB.
  • Under partial communication, the MIPC retains effective control by reconstructing sufficient system state information through observer-based estimation.
  • With a one-step (50ms) delay, performance degrades slightly, but the system remains stable; with a three-step (150ms) delay, performance deteriorates further but control remains effective.
  • In the no-communication scenario, the MIPC behaves similarly to a VSM, confirming that communication is essential for full performance, but the observer enables meaningful operation even with limited data.