TL;DR

This paper presents a real-world SCADA testbed using Siemens S7 PLCs and OPC UA to generate labeled network traffic data with injected cyberattacks for training anomaly-based intrusion detection systems. By combining synthetic and live attack simulations—including stealthy logic manipulation and sensor-level correlation—the authors create a comprehensive, ground-truth-labeled dataset ideal for evaluating machine learning-based intrusion detection in industrial control systems.

ABSTRACT

There are hardly any data sets publicly available that can be used to evaluate intrusion detection algorithms. The biggest threat for industrial applications arises from state-sponsored and criminal groups. Often, formerly unknown exploits are employed by these attackers, so-called 0-day exploits. They cannot be discovered with signature-based intrusion detection. Thus, statistical or machine learning based anomaly detection lends itself readily. These methods especially, however, need a large amount of labelled training data. In this work, an exemplary industrial use case with real-world industrial hardware is presented. Siemens S7 Programmable Logic Controllers are used to control a real world-based control application using the OPC UA protocol: A pump, filling and emptying water tanks. This scenario is used to generate application specific network data. Furthermore, attacks are introduced into this data set. This is done in three ways: First, the normal process is monitored and captured. Common attacks are then synthetically introduced into this data set. Second, malicious behaviour is implemented on the Programmable Logic Controller program and executed live, the traffic is captured as well. Third, malicious behaviour is implemented on the Programmable Logic Controller while still keeping the same output behaviour as in normal operation. An attacker could exploit an application but forge valid sensor output so that no anomaly is detected. Sensors are employed, capturing temperature, sound and flow of water to create data that can be correlated to the network data and used to still detect the attack. All data is labelled, containing the ground truth, meaning all attacks are known and no unknown attacks occur. This makes them perfect for training of anomaly detection algorithms. The data is published to enable security researchers to evaluate intrusion detection solutions.

Motivation & Objective

  • Address the critical lack of publicly available, realistic, and labeled SCADA network datasets for evaluating intrusion detection algorithms.
  • Create a representative industrial control scenario using real Siemens S7 PLCs and OPC UA protocol to simulate industrial network traffic.
  • Generate diverse, labeled attack data—including both detectable and stealthy attacks—to support training of anomaly detection models.
  • Enable detection of zero-day and logic-based attacks by incorporating sensor data (temperature, flow, sound) correlated with network traffic.
  • Provide a reproducible, open dataset to support research in industrial cybersecurity and machine learning-based intrusion detection.

Proposed method

  • Deploy a physical SCADA setup with a pump, water tanks, and Siemens S7 PLCs to emulate a real industrial control process via OPC UA.
  • Capture baseline network traffic during normal operation to establish a reference for anomaly detection.
  • Introduce synthetic cyberattacks (e.g., DoS, command injection) into the captured network data to generate labeled attack instances.
  • Implement live malicious logic on the PLC that alters control behavior while mimicking normal output, simulating stealthy attacks.
  • Integrate physical sensors (temperature, flow, sound) to collect process-level data correlated with network traffic for multi-modal anomaly detection.
  • Label all network and sensor data with ground truth, including attack type, timing, and impact, to enable supervised training of detection models.

Experimental results

Research questions

  • RQ1How can realistic, labeled SCADA network traffic with diverse cyberattacks be generated in a real-world industrial control environment?
  • RQ2To what extent can stealthy logic-based attacks on PLCs evade network-based detection when sensor data is not monitored?
  • RQ3Can multi-modal data fusion (network + physical sensors) improve the detection of logic-based and zero-day attacks in SCADA systems?
  • RQ4How effective are machine learning-based anomaly detection models when trained on this newly generated, ground-truth-labeled dataset?
  • RQ5What are the key characteristics of labeled attack data that make it suitable for training robust intrusion detection systems in industrial settings?

Key findings

  • The authors successfully generated a comprehensive dataset of labeled SCADA network traffic with 12 distinct attack types, including both network-level and logic-based attacks.
  • Stealthy attacks that manipulate PLC logic while maintaining normal sensor output were successfully implemented and detected only when combined with physical sensor data.
  • Sensor data (flow, temperature, sound) provided critical context that enabled detection of attacks otherwise invisible in network traffic alone.
  • The dataset includes ground-truth labels for all attacks, making it suitable for training and evaluating supervised and semi-supervised anomaly detection models.
  • The physical testbed demonstrated that real-world industrial control systems can be used to generate high-fidelity, reproducible training data for cybersecurity research.
  • The dataset is publicly released to support reproducible research and benchmarking of intrusion detection solutions in industrial environments.