[Paper Review] Modeling and Control of Hybrid Distribution Transformers for Simultaneous Grid Services
The paper presents an averaged three-phase model of a hybrid distribution transformer (HDT) with two back-to-back voltage source converters in series-shunt topology and demonstrates PI-based inner and outer controls enabling simultaneous grid services including voltage regulation, power factor correction, frequency regulation, and load phase balancing. Simulation in Python validates multi-service capability with simple, implementable control loops.
Hybrid distribution transformers (HDTs) integrate conventional transformers with partially rated power electronic converters to improve power quality, enable advanced ancillary services and increase penetration of renewable energy sources in the national power grid. In this paper, we present an averaged mathematical model of a three-phase HDT equipped with two back-to-back voltage source converters connected in a series-shunt configuration. Cascaded PI controllers are designed in the synchronously rotating dq0 reference frame to regulate load voltage, compensate reactive power, achieve grid frequency regulation, and perform load phase balancing. Simulation results implemented in Python confirm that these simple yet effective control mechanisms allow HDTs to offer simultaneous grid services without introducing complexity. The complete model, control architecture, and implementation steps are detailed, enabling further validation and adoption.
Motivation & Objective
- Motivate the use of hybrid distribution transformers to enhance grid stability and enable ancillary services in distribution networks.
- Develop an averaged three-phase HDT model with two back-to-back VSCs in series-shunt configuration.
- Design simple PI-based inner and outer control loops to achieve voltage regulation, reactive power compensation, frequency regulation, and phase balancing.
- Demonstrate through simulations that HDTs can deliver multiple services simultaneously with minimal cross-coupling and without high control complexity.
Proposed method
- Derive an averaged dynamic model for a three-phase HDT with two back-to-back VSCs in series-shunt topology using Kirchhoff’s laws.
- Implement inner PI controllers to compute duty cycles for VSC1 (grid-side) and VSC2 (load-side) from dq0-frame references.
- Design outer loops for DC-link voltage regulation, power factor correction, frequency regulation via a droop-based approach, and phase balancing in dq0 frame.
- Translate frequency deviations into active power references and then into load voltage setpoints tracked by inner loops.
- Validate with Python-based simulations across scenarios: voltage regulation, power factor correction, frequency response, phase balancing, and simultaneous services.
Experimental results
Research questions
- RQ1Can an averaged HDT model with simple PI controllers provide multiple grid services concurrently?
- RQ2How do inner and outer control loops interact when delivering voltage regulation, reactive power support, frequency regulation, and phase balancing?
- RQ3What are the performance characteristics (response time, stability) of HDTs under unbalanced loads and grid disturbances?
- RQ4Is there significant cross-coupling between services that would limit simultaneous operation?
- RQ5Can frequency response be effectively bid for in a realistic grid context using the proposed HDT control architecture?
Key findings
- The HDT model with two back-to-back VSCs can regulate load voltage and compensate reactive power using PI controllers.
- The outer loop enables DC-link voltage control, frequency regulation via a droop-based method, and power factor correction, all using dq0 references.
- The HDT can respond to grid disturbances within about a cycle for voltage regulation and achieve unity power factor with fast dq0 current tracking.
- Phase balancing is achievable by injecting corrective shunt currents while maintaining DC-link stability, with a quantifiable trade-off parameter gamma.
- Simultaneous delivery of voltage regulation, power factor correction, frequency regulation, and phase balancing is demonstrated with minimal service cross-coupling in simulations.
- The framework is analogous to UPQC, suggesting transferability to similar power quality devices.