Skip to main content
QUICK REVIEW

[Paper Review] MPC for Energy Efficient HVAC Control with Humidity and Latent Heat Considerations

Naren Srivaths Raman, Karthikeya Devaprasad|arXiv (Cornell University)|Mar 11, 2019
Building Energy and Comfort OptimizationEngineering20 references3 citations
TL;DR

This paper proposes a model predictive control (MPC) framework—SL-MPC—that explicitly incorporates humidity and latent heat in HVAC control for improved energy efficiency and occupant comfort. Using a low-order data-driven model of a cooling and dehumidifying coil, SL-MPC outperforms both a naive MPC (ignoring humidity) and a rule-based controller, particularly in maintaining indoor humidity within safe limits, with the key benefit being improved health outcomes over energy savings.

ABSTRACT

Even though energy efficient climate control of buildings using model predictive control (MPC) has been widely investigated, most MPC formulations ignore humidity and latent heat. The inclusion of moisture makes the problem considerably more challenging, primarily since a cooling and dehumidifying coil model which accounts for both sensible and latent heat transfers is needed. In this work, we propose an MPC controller in which humidity and latent heat are incorporated in a principled manner. We construct low order data-driven models of a cooling and dehumidifying coil that can be used in the MPC formulation. The resulting controller's performance is tested in simulation using a plant that differs significantly from the model used by the optimizer. Additionally, the performance of the proposed controller is compared with that of a naive MPC controller which does not explicitly consider humidity, and also to that of a conventional rule-based controller. Simulations show that the proposed MPC controller outperforms the other two consistently. It is also observed that the naive MPC formulation which does not consider humidity leads to poor humidity control under certain conditions. Such violations in humidity can adversely affect occupant comfort and health.

Motivation & Objective

  • Address the gap in existing MPC formulations for HVAC systems that ignore humidity and latent heat, which are critical for thermal comfort and health.
  • Overcome the challenge of modeling complex, nonlinear cooling and dehumidifying coil dynamics that couple sensible and latent heat transfer.
  • Develop a low-order, data-driven coil model suitable for real-time MPC optimization while maintaining accuracy.
  • Demonstrate through simulation that incorporating humidity and latent heat leads to superior performance in humidity control and long-term energy efficiency, even under plant-model mismatch.
  • Quantify the trade-offs between energy savings and occupant health, showing that the primary benefit of SL-MPC is avoiding long-term humidity-related risks like mold growth.

Proposed method

  • Develop a data-driven, low-order model of a cooling and dehumidifying coil that predicts conditioned air temperature and humidity as functions of inlet air and chilled water conditions (temperature, humidity, flow rate).
  • Use this model within an economic MPC framework to optimize control actions over a prediction horizon, minimizing energy use while satisfying thermal and humidity constraints.
  • Train the MPC model using data from simulations (e.g., EnergyPlus) or experiments, ensuring it captures the nonlinear coupling between sensible and latent heat transfer.
  • Validate the MPC controller using a higher-fidelity data-driven plant model that differs from the optimizer’s model to test robustness under model mismatch.
  • Compare SL-MPC against a naive MPC (ignoring humidity) and a rule-based controller (BL) across diverse weather conditions and occupancy scenarios.
  • Use a cost-benefit analysis to evaluate trade-offs between energy savings, humidity control, and long-term health impacts.

Experimental results

Research questions

  • RQ1How does incorporating humidity and latent heat in MPC affect indoor humidity control performance compared to standard MPC formulations that ignore these factors?
  • RQ2What is the impact of a naive MPC controller (ignoring humidity) on indoor humidity levels under mild outdoor weather conditions, such as spring/summer nights?
  • RQ3Can a data-driven, low-order coil model accurately represent the coupled sensible and latent heat transfer dynamics required for MPC in HVAC systems?
  • RQ4What is the relative trade-off between energy savings and occupant health when using SL-MPC versus conventional controllers?
  • RQ5How does the proposed SL-MPC controller perform under significant plant-model mismatch, and what does this imply for real-world deployment?

Key findings

  • The proposed SL-MPC controller significantly outperforms the naive MPC (S-MPC) in maintaining indoor humidity within acceptable limits, especially during mild, humid nights when S-MPC causes prolonged humidity violations.
  • The naive MPC controller leads to poor humidity control under mild weather conditions, with simulations showing space humidity exceeding limits for many hours, increasing the risk of mold growth and health issues.
  • While the energy savings of SL-MPC over S-MPC are modest (approximately 5%), the primary benefit lies in improved humidity control and occupant health, not energy reduction.
  • The rule-based controller (BL) ensures constraint satisfaction at the cost of higher energy use, demonstrating that conservative setpoints are effective but inefficient.
  • SL-MPC performs robustly even under large plant-model mismatch, indicating strong practical viability despite model inaccuracies.
  • The study reveals that long-term simulation is necessary to fully assess the benefits of humidity-aware MPC, as short-term evaluations may miss critical health-related impacts.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.