[Paper Review] Multiple model software for airflow and thermal building simulation. A case study under tropical humid climate, in R\'eunion Island

Harry Boyer, Jean-Claude Gatina|arXiv (Cornell University)|Dec 21, 2012
Wind and Air Flow StudiesEnvironmental Science7 citations
TL;DR

This paper presents CODYRUN, a multi-model building simulation software that selectively applies detailed or simplified thermal and airflow models to balance accuracy and computational efficiency. For a tropical humid building in Réunion Island, it demonstrates that using a non-linear convection model only in the primary zone reduces simulation time by ~50% while maintaining accuracy within 0.1°C and 0.1 kW of the full non-linear reference case.

ABSTRACT

The first purpose of our work has been to allow -as far as heat transfer modes, airflow calculation and meteorological data reconstitution are concerned- the integration of diverse interchangeable physical models in a single software tool for professional use, CODYRUN. The designer's objectives, precision requested and calculation time consideration, lead us to design a structure accepting selective use of models, taking into account multizone description and airflow patterns. With a building case study in Reunion Island, we first analyse the sensibility of the thermal model to diffuse radiation reconstitution on tilted surfaces. Then, a realistic balance between precision required and calculation time leads us to select detailed models for the zone of main interest, but to choose simplified models for the other zones.

Motivation & Objective

  • To develop a flexible simulation tool that allows selective application of thermal and airflow models based on design priorities.
  • To address the trade-off between simulation accuracy and computational time in multi-zone buildings.
  • To evaluate model sensitivity in tropical humid climates, particularly for diffuse radiation and convection models.
  • To demonstrate that selective use of detailed models in key zones improves efficiency without sacrificing accuracy.
  • To provide a practical framework for professional thermal simulation in complex, climate-sensitive buildings.

Proposed method

  • CODYRUN uses a tree-structured data model with Projects, Buildings, Zones, Inter-zones, and Components for modular input.
  • Thermal modeling employs finite difference nodal discretization and matrix condensation to solve energy balance equations.
  • Airflow is simulated via pressure-based network models with non-linear equations for flow through openings.
  • Convection models are selectively applied: linear (constant coefficient) for most zones, non-linear only in the primary zone of interest.
  • Meteorological data are reconstituted using different sky diffuse radiation models for sensitivity analysis.
  • Simulation results are compared across cases with varying model complexity to assess accuracy and time efficiency.

Experimental results

Research questions

  • RQ1How does the choice of diffuse radiation model on tilted surfaces affect thermal simulation accuracy in tropical climates?
  • RQ2What is the impact of using non-linear versus linear convection models on indoor temperature and cooling load predictions?
  • RQ3Can selective application of detailed models in key zones reduce simulation time while preserving accuracy?
  • RQ4What is the computational cost of applying non-linear convection models globally versus locally in a multi-zone building?
  • RQ5How do different model combinations affect the predicted cooling power requirements for thermal comfort?

Key findings

  • Using a non-linear convection model only in the main zone (Case C) reduced simulation time to 1.35 minutes per day, compared to 2.53 minutes in the full non-linear case (Case B).
  • The temperature error in Case C was only 0.1°C compared to the reference non-linear case (Case B), while Case A (global linear model) had an error of 1.2°C.
  • The cooling power error in Case C was 0.1 kW, significantly lower than the 0.5 kW error in Case A.
  • The time ratio between Case B and Case C was approximately 0.5, closely matching theoretical expectations based on zone-specific non-linear iterations.
  • The selective model approach achieved near-identical results to the full non-linear model in both temperature and power predictions, while halving computational cost.
  • The study confirms that model selection should be driven by zone-specific importance rather than global application, especially in energy-intensive simulations.