[Paper Review] Transient Stability Analysis of Grid- Connected Converters with Power Synchronization Control.
This paper analyzes the transient stability of grid-connected voltage-source converters using power synchronization control (PSC) via phase portrait analysis. It shows that PSC-VSCs remain synchronized if equilibrium points exist post-fault, with the critical clearing angle equal to the power angle at the unstable equilibrium point in post-fault conditions; notably, re-synchronization is still possible after one cycle of oscillation even beyond this angle, reducing system collapse risk.
The power synchronization control (PSC) has been increasingly used with voltage-source converters (VSCs) connected to the weak grid. This paper presents an in-depth analysis on the transient stability of the PSC-VSC by means of the phase portrait. It is revealed that the PSC-VSC will maintain synchronization with the grid as long as there are equilibrium points after the transient disturbance. However, during the grid faults without any equilibrium points, the critical clearing angle (CCA) for the PSC-VSC is found equal to the power angle at the unstable equilibrium point of the post-fault operation, which is crucial for the power system planning and protection. Moreover, the PSC-VSC can still re-synchronize with the grid after around one cycle of oscillation, even if the fault clearing angle is beyond the CCA. This feature reduces the risk of system collapse caused by the delayed fault clearance. Lastly, these findings are verified by simulations and experimental tests.
Motivation & Objective
- To investigate the transient stability of power synchronization-controlled voltage-source converters (PSC-VSCs) in weak grids.
- To determine the conditions under which PSC-VSCs maintain synchronization after fault disturbances.
- To identify the critical clearing angle (CCA) for fault clearing in PSC-VSC systems.
- To evaluate the system's ability to re-synchronize after fault clearance beyond the CCA.
- To validate the analytical findings through simulations and experimental tests.
Proposed method
- Phase portrait analysis is used to study the dynamic behavior of PSC-VSCs during and after transient disturbances.
- Equilibrium points are identified in both pre-fault and post-fault system conditions to assess stability.
- The critical clearing angle (CCA) is determined as the power angle corresponding to the unstable equilibrium point in the post-fault system.
- Stability is evaluated by analyzing the existence and nature of equilibrium points after fault clearing.
- Simulations and experimental tests are conducted to verify the analytical results.
Experimental results
Research questions
- RQ1What determines the transient stability of PSC-VSCs connected to weak grids?
- RQ2How does the existence of equilibrium points affect synchronization after a fault?
- RQ3What is the critical clearing angle (CCA) for PSC-VSCs during grid faults?
- RQ4Can PSC-VSCs re-synchronize after fault clearance beyond the CCA?
- RQ5How does the system behavior change when no equilibrium points exist post-fault?
Key findings
- The PSC-VSC maintains synchronization with the grid as long as equilibrium points exist after a transient disturbance.
- The critical clearing angle (CCA) for the PSC-VSC is equal to the power angle at the unstable equilibrium point in the post-fault system.
- Even when the fault clearing angle exceeds the CCA, the PSC-VSC can still re-synchronize after approximately one cycle of oscillation.
- This re-synchronization capability reduces the risk of system collapse due to delayed fault clearance.
- The analytical findings are confirmed through both simulation and experimental validation.