Skip to main content
QUICK REVIEW

[Paper Review] XFLEX HYDRO demonstrators grid services assessment and Ancillary Services Matrix elaboration

Christophe Nicolet, Matthieu Dreyer|arXiv (Cornell University)|Apr 9, 2024
Distributed and Parallel Computing SystemsComputer Science3 citations
TL;DR

This paper presents the XFLEX HYDRO Ancillary Service Matrix (ASM), a systematic assessment of six hydropower demonstrators—four pumped storage plants, one conventional hydro plant, and one run-of-river plant—evaluating their capacity to deliver grid support services. Using 1D validated simulation models enhanced with control system dynamics, the study quantifies active power response across ancillary services, scoring each demonstrator from 0 to 5 to rank technology performance and identify key benefits of variable speed drives, SPPS, hydraulic short circuit, and hydro-battery-hybrid systems.

ABSTRACT

This paper presents the methodology and key results which enabled to establish the so-called Ancillary Service Matrix (ASM) presenting the ability to deliver the different ancillary services of each of the 6 demonstrators of the XFLEX HYDRO research project combined with the applicable technologies studied in this analysis. These technologies include i) the variable speed technology with Doubly Fed Induction Machine (DFIM) or Full Size Frequency Converters (FSFC), ii) the Smart Power Plant Supervisor (SPPS) enabling to extend the operating range of the hydraulic units in turbine mode based on a better knowledge of the hydro unit wear and tear and associated costs over the full unit operating range, iii) the hydraulic short circuit (HSC) operation leading to simultaneous operation of pump and turbines of Pumped Storage Power Plants (PSPP) and iv) the Hydro-Battery-Hybrid (HBH) applied at Run-of-River demonstrator. The demonstrators considered for this study includes 4 pumped storage power plants, 1 conventional hydro storage plant and 1 run-of-the-river plant. For each demonstrator a 1D simulation model was developed and validated and was further enhanced to include the model of control system enabling to address the various ancillary services. The systematic 1D numerical simulation of ancillary service contribution of each demonstrator and related technologies enabled to quantify the magnitude of active power response to contribute to the different grid services. The results have been scored between 0 and 5 for each ancillary service, allowing to populate the Ancillary Service Matrix which is summarizing the results in a graphical and synthetic way. The analysis of the score of the Ancillary Services Matrix enables the reader to draw several key conclusions about the benefits unlocked by the implementation of these technologies which are summarized in the paper.

Motivation & Objective

  • To evaluate the grid service capabilities of six diverse hydropower demonstrators within the XFLEX HYDRO project.
  • To quantify the contribution of advanced technologies—such as variable speed drives, SPPS, hydraulic short circuit, and hydro-battery-hybrid systems—to ancillary services.
  • To develop a standardized, visual, and synthetic Ancillary Service Matrix (ASM) for comparing technology performance across demonstrators.
  • To support grid integration of hydropower by identifying optimal technology configurations for enhanced grid support.
  • To provide a decision-support framework for grid operators and project developers based on quantified performance scores (0–5) for each service.

Proposed method

  • Developed 1D dynamic simulation models for each of the six hydropower demonstrators, validated against operational data.
  • Enhanced the 1D models to include detailed control system dynamics for turbine, pump, and hybrid operation modes.
  • Simulated active power response across multiple ancillary services (e.g., frequency regulation, spinning reserve, black start) under various grid disturbance scenarios.
  • Applied a scoring system (0–5) to quantify each demonstrator’s capability for each ancillary service based on simulation results.
  • Integrated all scores into a visual Ancillary Service Matrix (ASM) to enable cross-technology and cross-demonstrator comparison.
  • Evaluated four key technologies: (i) variable speed with DFIM or FSFC, (ii) Smart Power Plant Supervisor (SPPS), (iii) Hydraulic Short Circuit (HSC), and (iv) Hydro-Battery-Hybrid (HBH).

Experimental results

Research questions

  • RQ1How do variable speed technology and SPPS improve the ancillary service capabilities of hydropower plants compared to conventional systems?
  • RQ2To what extent can hydraulic short circuit operation enhance the response speed and flexibility of pumped storage plants?
  • RQ3What is the impact of integrating battery storage via HBH on the ancillary service performance of run-of-river plants?
  • RQ4How do different control strategies and operating ranges affect the quantified grid service performance across the six demonstrators?
  • RQ5What is the relative performance ranking of each demonstrator and technology combination across key ancillary services using a standardized scoring framework?

Key findings

  • The Ancillary Service Matrix (ASM) successfully visualized and ranked the performance of all six demonstrators across multiple ancillary services using a 0–5 scoring system.
  • Variable speed technology with FSFC or DFIM significantly improved response time and operating range, particularly for primary frequency control and voltage support.
  • The Smart Power Plant Supervisor (SPPS) enabled extended turbine operation into previously restricted zones by modeling wear and cost trade-offs, enhancing grid service availability.
  • Hydraulic Short Circuit (HSC) operation demonstrated the potential for near-instantaneous active power response due to simultaneous pump and turbine operation in PSPPs.
  • The Hydro-Battery-Hybrid (HBH) configuration at the run-of-river demonstrator enhanced frequency regulation and black start capability through fast-responding battery storage.
  • The ASM revealed that technology integration—especially SPPS and HBH—led to higher overall scores, indicating substantial grid service potential beyond conventional hydropower.

Read this paper

Open the full text in the Nubint reader and ask about any passage as you read.

Read this paper on Nubint

This review was generated by AI from the original paper. Please check the paper before citing it.