TL;DR

This paper formulates time-variant virtual inertia control from energy storage as an optimal control problem using structure-preserving power system models, incorporating bus frequency, power, and energy constraints. It employs dynamic programming and PROPT MATLAB software to compute globally optimal virtual inertia trajectories, demonstrating effectiveness in minimizing frequency deviations and power oscillations in a 12-bus system under large disturbances.

ABSTRACT

The integration of renewables gradually replaces the traditional power plants, and this makes that the rotational inertia provided by the power plants is decreasing with time. Virtual inertia emulated by power electronic devices is becoming a promising way to stabilize the frequency of power system when a disturbance happens. And how to control virtual inertia to achieve desired performance is an important question to be answered. In this work, authors formulate an optimal control problem to describe the behaviour of controlling the time-variant inertia from storage, and structure preserving model is utilized to describe the dynamics of system, where frequencies of all buses are preserved. Also, practical constraints such as frequency contraints for buses, power/energy constraints for storage are incorporated in the optimal control problem. To solve this optimal control problem, dynamic programming (DP) and PROPT MATLAB Optimal Control Software are employed to obtain global optimal solution (virtual inertia trajectory). The simulation results show the correctness and effectiveness of our problem formulation and solving method.

Motivation & Objective

  • Address the challenge of stabilizing low-inertia power systems with increasing renewable integration by enabling time-variant virtual inertia from storage.
  • Formulate an optimal control problem that preserves individual bus frequency dynamics, unlike aggregated models.
  • Incorporate practical constraints such as frequency limits, power/energy capacity, and transient performance requirements.
  • Develop a globally optimal solution method for virtual inertia trajectories that outperforms fixed-parameter or locally optimized approaches.
  • Enable application to diverse power electronic interfaces by using flexible, model-agnostic optimization techniques.

Proposed method

  • Formulate a structure-preserving optimal control problem using the swing equation model to represent frequency dynamics at all buses.
  • Define the virtual inertia of storage devices as time-varying control inputs, with bounds on inertia and energy capacity.
  • Integrate constraints on bus frequency (lower and upper limits), power injection, and energy storage capacity into the optimal control framework.
  • Apply dynamic programming to solve the optimal control problem for general system dynamics, ensuring global optimality.
  • Use PROPT MATLAB software to solve high-dimensional optimal control problems efficiently, especially for complex, large-scale systems.
  • Employ symbolic processing and numerical integration to compute optimal trajectories and evaluate performance metrics such as frequency deviation and power flow oscillations.

Experimental results

Research questions

  • RQ1How can virtual inertia from storage be optimally controlled over time to stabilize system frequency during large disturbances?
  • RQ2What is the impact of spatial distribution of storage on frequency dynamics across multiple buses?
  • RQ3Can global optimal virtual inertia trajectories be computed under realistic constraints such as frequency limits and energy capacity?
  • RQ4How do different control objectives—minimizing frequency deviation, minimizing power oscillations, or minimizing total energy usage—affect the optimal inertia trajectory?
  • RQ5How does the combination of dynamic programming and PROPT software enable efficient and accurate solution of high-dimensional optimal control problems in power systems?

Key findings

  • The proposed optimal control formulation successfully preserves individual bus frequency dynamics, avoiding the limitations of aggregated second-order models.
  • Simulation results show a 1.4975 p.u.·s reduction in integrated frequency absolute value when minimizing frequency deviations, confirming effective stabilization.
  • The method achieved a 3.5128s symbolic processing time and 247.65s CPU time for the frequency minimization case, demonstrating feasibility for real-time analysis.
  • Even with an expanded inertia range [0.1s, 15s], the effect on minimizing power flow oscillations was limited, indicating that virtual inertia control alone may not be sufficient for this objective.
  • The power peak was reduced to 1.7853 p.u. at t=9s in the oscillation-minimization case, showing measurable improvement in transmission line stability.
  • The combination of dynamic programming and PROPT enables global optimality and high computational efficiency, making it suitable for complex, multi-bus power systems with detailed dynamics.